2017-08-21 09:13:492ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061303
 8/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AC-1: MAKEUP AIR IS REQUIRED FOR THE NEW 625
 CFM EXHAUST HOOD- SECTION 505.2 FBC-14 MECHANICAL. THE
 RATE OF AIR PROVIDED SHALL BE APPROXIMATELY EQUAL TO
 THE EXHAUST AIR RATE.
  
 2) AC-1: SHOW THE POINT OF CONNECTION OF THE NEW HOOD
 EXHAUST VENT TO THE EXISTING VENT SYSTEM.
  