| Plan Review Notes For Permit 17061303 |
| Permit Number |
17061303 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-21 09:13:49 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061303 | | | 8/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET AC-1: MAKEUP AIR IS REQUIRED FOR THE NEW 625 | | | CFM EXHAUST HOOD- SECTION 505.2 FBC-14 MECHANICAL. THE | | | RATE OF AIR PROVIDED SHALL BE APPROXIMATELY EQUAL TO | | | THE EXHAUST AIR RATE. | | | | | | 2) AC-1: SHOW THE POINT OF CONNECTION OF THE NEW HOOD | | | EXHAUST VENT TO THE EXISTING VENT SYSTEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|