| Plan Review Notes For Permit 17061303 |
| Permit Number |
17061303 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-13 18:23:47 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061303 | | | 7/13/17 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) SHEET A-3: SHOW THE LOCATION OF DEMOLITION KEY NOTE | | | D10 ON THE FLOOR PLAN. | | | | | | 2) PROVIDE MECHANICAL PLANS SHOWING ALL PROPOSED | | | CHANGES TO THE EXISTING HVAC SYSTEMS. | | | | | | 3) CLARIFY IF ANY CHANGES TO THE KITCHEN EXHAUST | | | VENTILATION ARE PROPOSED SUCH AS A NEW EXHAUST HOOD AND | | | DUCT. PROVIDE DETAILS IF APPLICABLE AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE COOK TOP AND | | | EXHAUST HOOD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|