2017-07-12 09:25:57CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL RISER NOTE #5 STATES THAT AFCI PROTECTION
 SHALL BE "PER NEC 2010-12". THIS IS NOT A VALID CODE
 SECTION, PLEASE CORRECT. NEC 210.12; FBC 107.2.1
 2. ELECTRICAL RISER NOTE #6 STATES TAMPER RESISTANT
 RECEPTACLES "PER NEC 406.11". THIS CODE SECTION DOES
 NOT APPLY TO TAMPER RESISTANT. PROVIDE CORRECTION. NEC
 406.12; FBC 107.2.1
 3. AFCI PROTECTION IS REQUIRED FOR MORE THAN JUST
 RECEPTACLES. INDICATE AFCI PROTECTION PER CODE: "ALL
 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12
 4. SCOPE OF WORK ON A-1 STATES THAT THE ELECTRICAL
 PANEL WILL BE RELOCATED. PLAN ONLY SHOWS THE EXISTING
 LOCATION. SHOW NEW LOCATION ON PLAN. FBC 107.2.1
 5. SMOKE ALARMS SHOULD BE INSTALLED IN EACH BEDROOM AND
 ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
 THESE SHOULD BE FED FROM SAME POWER SOURCE,
 INTERCONNECTED, AND NOT TIED TO THE BUILDING FIRE ALARM
 SYSTEM. THERE IS A NOTE IN THE SYMBOLS LEGEND THAT
 STATES TO CONNECT TO BUILDING FIRE ALARM SYSTEM. REMOVE
 AND/OR REVISE THIS NOTE AND PROVIDE CORRECTIONS FOR
 ITEMS PREVIOUSLY STATED. FBC 907.2.11.2; NFPA 101,
 9.6.2.10.4
 6. THE SPECS FOR THE TANKLESS WATER HEATER SPECIFIED ON
 PLUMBING PLAN DOES NOT MATCH THE DATA IN THE PANEL
 SCHEDULE. PROVIDE CORRECTION FOR WIRE AND BREAKER SIZE,
 ADJUST LOAD CALCULATION ACCORDINGLY. NEC 110.3, 240.4,
 310.15(B)(16)
 7. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. MASTER CLOSET SHOWS
 STANDARD RECESS LIGHTS. PROVIDE CORRECTION. NEC
 410.16(B)
 8. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. THESE AREAS SHOW STANDARD
 RECESS LIGHTS. PROVIDE CORRECTION. NEC 410.10(D)
 9. NOTE FOR ENERGY COMPLIANCE IN THE SYMBOLS LEGEND IS
 NOT CORRECT. "A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS". PROVIDE CORRECTION. FBC EC
 R404.1
 10. PLAN SHOWS A GFCI OUTLET BY THE TUB IN MASTER BATH.
 RECEPTACLES ARE NOT PERMITTED IN THIS LOCATION.
 HOWEVER, THIS COULD BE FOR A JACUZZI TUB, BUT THE PLAN
 IS UNCLEAR AND THERE IS NO CIRCUIT LISTED FOR A JACUZZI
 TYPE TUB IN THE PANEL SCHEDULE. CORRECT AND/OR CLARIFY.
 FBC 107.2.1; NEC 406.9(C)
 11. LIVING ROOM TV SHOWS A CABLE OUTLET AT 60", BUT
 DOES NOT SHOW A RECEPTACLE AT THE SAME HEIGHT. WILL
 THERE BE ONE LOCATED HERE? CORRECT AND/OR CLARIFY. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  