Plan Review Notes
Plan Review Notes For Permit 17061303
Permit Number 17061303
Review Stop B
Sequence Number 1
Notes
Date Text
2017-07-07 15:15:122014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061303
 ADD: 701 S. OLIVE AVE. SUITE NUMBER 619
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-719-0725/ MICHAEL COLAPRETE
 E-MAIL: ???????? WE PREFER TO COMMUNICATE BY E-MAIL!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 07/2017
 ACTION: DENIED
  
 1A) SHEET A-1 THE DOOR SCHEDULE INDICATES DOORS 4, 6,
 9, 10, 11, 12, 13 & 14 ALL BEING 2 FT. 8 INCHES WIDE.
 2014 FBC-EXISTING BUILDING CODE 301.1 THE DOORS CANNOT
 BE LESS COMPLIANT THAN AT THE TIME THE BUILDING WAS
 BUILT. THE ORIGINAL BUILDING WAS BUILT UNDER PERMIT
 04120353 IN OTHER WORDS APPLIED FOR PERMIT APRIL OF
 2004. BUILDINGS THAT WERE IN DESIGN OR PERMITTED FOR
 FIRST OCCUPANCY AFTER 13, 1991 MUST BE DESIGNED FOR
 FAIR HOUSING. THE INTERIOR DOORS ARE CONSIDERED USABLE
 DOORS UNDER FAIR HOUSING THAT ALLOWS PASSAGE WITHIN THE
 DWELLING UNIT. USABLE DOORS ARE INTENDED TO PROVIDE 32
 INCHES CLEAR WIDTH. PLEASE SEE THE 2014
 FBC-ACCESSIBILITY CODE/ FAIR HOUSING REQUIREMENT 3.
 USABLE DOORS, FIGURE 1 (A) HINGED DOORS & ( C ) FOR
 SLIDING OR POCKET DOORS.
  
 1B) SHEET A-1 THE FLOOR PLAN INDICATES A NEW ISLAND
 CABINET AND COUNTERTOP AND A DISTANCE OF 39 INCHES
 BETWEEN THE ISLAND AND THE BACK WALL. PLEASE SEE FAIR
 HOUSING REQUIREMENTS UNDER REQUIREMENT 7 FOR USABLE
 KITCHENS (B) CLEARANCE BETWEEN COUNTERS AND ALL
 OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES
 (REFRIGERATOR DOORS) OR WALLS IS AT LEAST 40 INCHES.
  
 2) SHEET A2 DETAILS 1-3 PROVIDE THE TYPE OF ANCHOR AND
 SPACING FOR THE FRAMING MEMBERS FOR THE DROP CEILING
 BUT MISSING THE ANCHOR AND SPACING FOR THE 7/8 INCH
 HI-HAT METAL. PLEASE PROVIDE ADDITIONAL INFORMATION.
 107.2.1.3.
  
 3) SHEET A2 TOP OF PAGE PALM BEACH COUNTY CONSTRUCTION
 NOTES. PLEASE NOTE THE JOB SITE LOCATION IS NOT IN PALM
 BEACH COUNTY UNINCORPORATED BUT IN THE CITY OF WEST
 PALM BEACH, THESE NOTES ARE NOT APPLICABLE! 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 4) THE PLANS DO NOT STATE IF THE FLOORS ARE BEING
 REMOVED, IF THEY ARE IN ANY ROOM AND EITHER MARBLE,
 TILE, WOOD LAMINATES OR VINYL FLOORING ARE BEING
 INSTALLED THEN COMPLIANCE WITH THESE SECTIONS OF THE
 2014 FBC-B WILL BE REQUIRED:
  
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  