| 2017-07-07 15:15:12 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17061303 |
| | ADD: 701 S. OLIVE AVE. SUITE NUMBER 619 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-719-0725/ MICHAEL COLAPRETE |
| | E-MAIL: ???????? WE PREFER TO COMMUNICATE BY E-MAIL!!! |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 07/2017 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET A-1 THE DOOR SCHEDULE INDICATES DOORS 4, 6, |
| | 9, 10, 11, 12, 13 & 14 ALL BEING 2 FT. 8 INCHES WIDE. |
| | 2014 FBC-EXISTING BUILDING CODE 301.1 THE DOORS CANNOT |
| | BE LESS COMPLIANT THAN AT THE TIME THE BUILDING WAS |
| | BUILT. THE ORIGINAL BUILDING WAS BUILT UNDER PERMIT |
| | 04120353 IN OTHER WORDS APPLIED FOR PERMIT APRIL OF |
| | 2004. BUILDINGS THAT WERE IN DESIGN OR PERMITTED FOR |
| | FIRST OCCUPANCY AFTER 13, 1991 MUST BE DESIGNED FOR |
| | FAIR HOUSING. THE INTERIOR DOORS ARE CONSIDERED USABLE |
| | DOORS UNDER FAIR HOUSING THAT ALLOWS PASSAGE WITHIN THE |
| | DWELLING UNIT. USABLE DOORS ARE INTENDED TO PROVIDE 32 |
| | INCHES CLEAR WIDTH. PLEASE SEE THE 2014 |
| | FBC-ACCESSIBILITY CODE/ FAIR HOUSING REQUIREMENT 3. |
| | USABLE DOORS, FIGURE 1 (A) HINGED DOORS & ( C ) FOR |
| | SLIDING OR POCKET DOORS. |
| | |
| | 1B) SHEET A-1 THE FLOOR PLAN INDICATES A NEW ISLAND |
| | CABINET AND COUNTERTOP AND A DISTANCE OF 39 INCHES |
| | BETWEEN THE ISLAND AND THE BACK WALL. PLEASE SEE FAIR |
| | HOUSING REQUIREMENTS UNDER REQUIREMENT 7 FOR USABLE |
| | KITCHENS (B) CLEARANCE BETWEEN COUNTERS AND ALL |
| | OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES |
| | (REFRIGERATOR DOORS) OR WALLS IS AT LEAST 40 INCHES. |
| | |
| | 2) SHEET A2 DETAILS 1-3 PROVIDE THE TYPE OF ANCHOR AND |
| | SPACING FOR THE FRAMING MEMBERS FOR THE DROP CEILING |
| | BUT MISSING THE ANCHOR AND SPACING FOR THE 7/8 INCH |
| | HI-HAT METAL. PLEASE PROVIDE ADDITIONAL INFORMATION. |
| | 107.2.1.3. |
| | |
| | 3) SHEET A2 TOP OF PAGE PALM BEACH COUNTY CONSTRUCTION |
| | NOTES. PLEASE NOTE THE JOB SITE LOCATION IS NOT IN PALM |
| | BEACH COUNTY UNINCORPORATED BUT IN THE CITY OF WEST |
| | PALM BEACH, THESE NOTES ARE NOT APPLICABLE! 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4) THE PLANS DO NOT STATE IF THE FLOORS ARE BEING |
| | REMOVED, IF THEY ARE IN ANY ROOM AND EITHER MARBLE, |
| | TILE, WOOD LAMINATES OR VINYL FLOORING ARE BEING |
| | INSTALLED THEN COMPLIANCE WITH THESE SECTIONS OF THE |
| | 2014 FBC-B WILL BE REQUIRED: |
| | |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |