| Plan Review Notes For Permit 17061260 |
| Permit Number |
17061260 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-04-24 14:44:50 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061260 | | | 4/24/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ACCUREX MODEL XRRS RESIDENTIAL RECIRCULATION | | | HOOD IS NOT UL 710B LISTED AND THEREFORE CANNOT BE | | | INSTALLED IN A COMMERCIAL KITCHEN. PLEASE NOTE THAT | | | HOODS THAT ARE UL 710B LISTED DO NOT HAVE TO BE IN | | | COMPLIANCE WITH SECTION 507.12 WHICH REQUIRES THE 6" | | | OVERHANG- SEE SECTION 507.1 EXCEPTION 2. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|