Plan Review Notes
Plan Review Notes For Permit 17061260
Permit Number 17061260
Review Stop M
Sequence Number 3
Notes
Date Text
2018-04-24 14:44:503RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17061260
 4/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ACCUREX MODEL XRRS RESIDENTIAL RECIRCULATION
 HOOD IS NOT UL 710B LISTED AND THEREFORE CANNOT BE
 INSTALLED IN A COMMERCIAL KITCHEN. PLEASE NOTE THAT
 HOODS THAT ARE UL 710B LISTED DO NOT HAVE TO BE IN
 COMPLIANCE WITH SECTION 507.12 WHICH REQUIRES THE 6"
 OVERHANG- SEE SECTION 507.1 EXCEPTION 2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  