Plan Review Notes
Plan Review Notes For Permit 17061260
Permit Number 17061260
Review Stop B
Sequence Number 3
Notes
Date Text
2018-04-19 15:43:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061260
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES
 TEL: 561-803-8100
 E-MAIL: MIACOBUCCICSSBUILDS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. APRIL 19, 2018
 ACTION: DENIED
  
 1) COMPLIED.
  
 2A) 3RD REVIEW. THIS REVIEW THERE ARE (4) MIAMI-DADE
 NOA 15-0820.06 SUBMITTED NONE OF THE SCHEDULES ON THE 4
 TECHNICAL SHEETS CIRCLED TO IDENTIFY WHICH SUB-SYSTEM,
 SIZE OF BRACKET/ UNIT, ANCHOR AND TYPE OF MATERIAL THE
 ANCHOR IS TO BE FASTEN. 107.2.1.3/ , 1609.6.4.4.1
 COMPONENTS & CLADDING. RULE 61G-20-3.
 THERE IS A 2ND WHAT APPEARS TO BE A SHOP DRAWING FROM
 THE METAL SHOP, NOT A PRODUCT APPROVAL, NO COVER PAGE
 FOR A FLORIDA OR MIAMI-DADE NOA. 107.2.1.3/ ,
 1609.6.4.4.1 COMPONENTS & CLADDING. RULE 61G-20-3.
  
 1ST ROUND COMMENT. THE SUBMITTED MIAMI-DADE NOA
 15-0820.06 WAS SUBMITTED BUT NONE OF THE TABLES ON THE
 TECHNICAL SHEETS IDENTIFY THE UNIT SIZE / BRACKET, WALL
 TYPE, ANCHOR TYPE, MINIMUM EMBEDMENT, MINIMUM E. D.,
 RISK CATEGORY, BUILDING HEIGHT, ETC.? FBC-B 2014 FBC-B
 1604.4 ANALYSIS.
  
 2B) SUBMITTED WALL BRACKET FROM THE METAL SHOP THERE IS
 NO PRODUCT APPROVAL FOR THIS WALL BRACKET. IT HAS AN
 ENGINEERS SEAL JOSEPH HILLER, THE SEAL IS NOT A LEGAL
 SIZE SEAL AND THE SIGNATURE IS A COPY. EITHER THE
 PRODUCT APPROVAL NEEDS TO BE EITHER A MIAMI-DADE NOA OR
 FLORIDA APPROVAL. IT WOULD APPEAR THIS ALUMINUM WALL
 BRACE WOULD NEED TO BE EITHER A LOCAL APPROVAL OR A
 SITE SPECIFIC APPROVAL.
  
 3) 3RD REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED.
  
 5) COMPLIED. ROLLING GARAGE DOOR IS DELETED FROM THE
 PROJECT.
  
 6) SEMI- COMPLIED. HOOD WILL BE DETERMINED BY THE
 MECHANICAL REVIEWER IF CODE COMPLIANT PLEASE NOTE THE
 COMMENT STANDS. PLEASE SEE THE DEFINITION OF A
 COMMERCIAL KITCHEN UNDER THE 2014 FBC- MECHANICAL CODE.
 COMMERCIAL COOKING APPLIANCES. FOR THE PURPOSE OF THIS
 DEFINITION, A FOOD SERVICE ESTABLISHMENT SHALL INCLUDE
 ANY BUILDING OR A PORTION THEREOF USED FOR THE
 PREPARATION AND SERVING OF FOOD. APPLIANCES USED IN A
 COMMERCIAL FOOD SERVICE ESTABLISHMENT FOR HEATING OR
 COOKING FOOD AND WHICH PRODUCE GREASE VAPORS, STEAM,
 FUMES, SMOKE OR ODORS THAT ARE REQUIRED TO BE REMOVED
 THROUGH A LOCAL EXHAUST VENTILATION SYSTEM. SUCH
 APPLIANCES INCLUDE DEEP FAT FRYERS; UPRIGHT BROILERS;
 GRIDDLES; BROILERS; STEAM-JACKETED KETTLES; HOT-TOP
 RANGES; UNDER-FIRED BROILERS (CHAR BROILERS); OVENS;
 BARBECUES; ROTISSERIES; AND SIMILAR APPLIANCES.
  
 904.2 WHERE REQUIRED. AUTOMATIC FIRE-EXTINGUISHING
 SYSTEMS INSTALLED AS AN ALTERNATIVE TO THE REQUIRED
 AUTOMATIC SPRINKLER SYSTEMS OF SECTION 903 SHALL BE
 APPROVED BY THE FIRE CODE OFFICIAL. AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS SHALL NOT BE CONSIDERED
 ALTERNATIVES FOR THE PURPOSES OF EXCEPTIONS OR
 REDUCTIONS ALLOWED BY OTHER REQUIREMENTS OF THIS CODE.
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH REQUIRED
 COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEM
 REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR CHAPTER
 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO HAVE A
 TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 7) 3RD. SHEET A-101 DETAIL #9 ILLUSTRATES THE USE OF A
 WALL OVEN, WHEN SCALED THE OPERATING KNOBS ARE LOCATED
 AT 4 FT. 9 INCHES ABOVE THE FINISH FLOOR OUT OF RANGE
 FOR REACH RANGES IN 308 OF THE ACCESSIBILITY CODE AND
 309 OPERABLE PARTS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  