| 2017-08-25 08:34:49 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17061260 |
| | 8/25/17 |
| | |
| | 1) COMPLY WITH BUILDING REVIEW COMMENTS REGARDING THE |
| | CONDENSER RACK. |
| | |
| | 2) TYPE II EXHAUST HOODS ARE REQUIRED FOR THE NEW |
| | COOKING APPLIANCES PER SECTION 507.2.3. THE HOODS MUST |
| | BE CONSTRUCTED WITH MATERIALS THAT ARE IN COMPLIANCE |
| | WITH SECTION 507.5- NO, 22 GAUGE STEEL OR NO. 24 GAGE |
| | STAINLESS STEEL. THE SUBMITTED SPEC SHEET FOR THE |
| | ELECTROLUX RANGE HOOD DOES NOT PROVIDE DATA TO SHOW |
| | COMPLIANCE. PLEASE NOTE THAT ONLY ONE HOOD IS SHOWN ON |
| | |
| | THE PLANS HOWEVER THERE ARE TWO HEAT PRODUCING |
| | APPLIANCES. IF THE INTENTION IS NOT TO PROVIDE A HOOD |
| | FOR THE WALL OVEN, PLEASE REFER TO SECTION 507.2.2 AND |
| | PROVIDE EXHAUST VENTILATION AT A RATE OF 0.70 USING 100 |
| | SQ. FT. AS THE OCCUPYING EXHAUST AREA OF THE APPLIANCE. |
| | |
| | 3) PLEASE PROVIDE A DIMENSIONED ELEVATION VIEW OF THE |
| | HOOD OVER THE OVEN THAT INDICATES THE MINIMUM 6" |
| | OVERHANG OF THE HOOD ON EACH SIDE OF THE APPLIANCE, AND |
| | THE DISTANCE BETWEEN THE FRONT LOWER LIP OF THE HOOD |
| | AND THE COOKING SURFACE- SECTION 507.12. |
| | |
| | 4) AUTOMATICALLY CONTROLLED MAKE UP AIR IS REQUIRED FOR |
| | THE HOODS AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST |
| | RATE- SECTION 508.1. THE TEMPERATURE DIFFERENTIAL |
| | BETWEEN THE MAKE UP AIR AND THE AIR IN THE CONDITIONED |
| | SPACE SHALL NOT EXCEED 10 DEGREES F- SECTION 508.1.1. |
| | |