2017-08-25 08:34:492ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061260
 8/25/17
  
 1) COMPLY WITH BUILDING REVIEW COMMENTS REGARDING THE
 CONDENSER RACK.
  
 2) TYPE II EXHAUST HOODS ARE REQUIRED FOR THE NEW
 COOKING APPLIANCES PER SECTION 507.2.3. THE HOODS MUST
 BE CONSTRUCTED WITH MATERIALS THAT ARE IN COMPLIANCE
 WITH SECTION 507.5- NO, 22 GAUGE STEEL OR NO. 24 GAGE
 STAINLESS STEEL. THE SUBMITTED SPEC SHEET FOR THE
 ELECTROLUX RANGE HOOD DOES NOT PROVIDE DATA TO SHOW
 COMPLIANCE. PLEASE NOTE THAT ONLY ONE HOOD IS SHOWN ON
  
 THE PLANS HOWEVER THERE ARE TWO HEAT PRODUCING
 APPLIANCES. IF THE INTENTION IS NOT TO PROVIDE A HOOD
 FOR THE WALL OVEN, PLEASE REFER TO SECTION 507.2.2 AND
 PROVIDE EXHAUST VENTILATION AT A RATE OF 0.70 USING 100
 SQ. FT. AS THE OCCUPYING EXHAUST AREA OF THE APPLIANCE.
  
 3) PLEASE PROVIDE A DIMENSIONED ELEVATION VIEW OF THE
 HOOD OVER THE OVEN THAT INDICATES THE MINIMUM 6"
 OVERHANG OF THE HOOD ON EACH SIDE OF THE APPLIANCE, AND
 THE DISTANCE BETWEEN THE FRONT LOWER LIP OF THE HOOD
 AND THE COOKING SURFACE- SECTION 507.12.
  
 4) AUTOMATICALLY CONTROLLED MAKE UP AIR IS REQUIRED FOR
 THE HOODS AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST
 RATE- SECTION 508.1. THE TEMPERATURE DIFFERENTIAL
 BETWEEN THE MAKE UP AIR AND THE AIR IN THE CONDITIONED
 SPACE SHALL NOT EXCEED 10 DEGREES F- SECTION 508.1.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER