Plan Review Notes
Plan Review Notes For Permit 17061260
Permit Number 17061260
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-08-22 14:36:542ND REVIEW RESPONSE
  
  
 ORIGINAL COMMENTS:
  
 1) ANY WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE AREA OF THE KITCHEN INDICATES A NEW WALL; P 1.
 ANYTIME A WALL IS REMOVED AND/OR ADDED IN AN EXISTING
 SPRINKLERED BUILDING, A REVIEW OF THE PROTECTION
 COVERAGE IS REQUIRED. THE PROPOSED PROJECT REQUIRES A
 REVIEW OF THE SPRINKLER COVERAGE BY A DESIGN
 PROFESSIONAL TO DETERMINE PROPER CODE COVERAGE.
  
 THIS CAN NO LONGER BE A PROVISO COMMENT.
  
 A NOTE SHALL BE ADDED TO THE SUBMITTED THAT ANY WORK ON
 THE FIRE SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 SHOULD INCOMPLETE FIRE SPRINKLER COVERAGE BE FOUND
 DURING FIRE INSPECTIONS THE INSPECTION WILL FAIL UNTIL
 PROPER COVERAGE IS COMPLETED.
  
  
  
 2) A RANGE AND HOOD VENT IS INDICATED. PER NFPA 101,
 THE SYSTEMS SHALL BE INSTALLED PER NFPA 96 AND WITH A
 SEPARATE FIRE SUPPRESSION SYSTEM. THE HOOD SYSTEM AND
 FIRE SUPPRESSION SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 PER NFPA 101, CHAPTER 13, EXISTING ASSEMBLY OCCUPANCIES
 AND CHAPTER 39, EXISTING BUSINESS OCCUPANCIES COOKING
 EQUIPMENT SHALL BE PROTECTED:
  
 13.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 39.3.2.3 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 THE PROPOSED EQUIPMENT DOES NOT MEET THESE REQUIREMENTS
 AND SHALL BE PROTECTED ACCORDINGLY. THE STOVE AND RANGE
 TOP WOULD HAVE TO REMOVED AND REPLACED WITH EQUIPMENT
 DESIGNED TO WARM FOOD ONLY OR A SUPPRESSION SYSTEM
 WOULD NEED TO BE INSTALLED.
  
 THIS COMMENT CAN NO LONGER BE A PROVISO COMMENT. SEE
 ALSO THE BUILDING REVIEW COMMENT.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved