Plan Review Notes
Plan Review Notes For Permit 17061260
Permit Number 17061260
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-17 16:20:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061260
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES
 TEL: 561-803-8100
 E-MAIL: MIACOBUCCICSSBUILDS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. AUGUST 17, 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) THIS REVIEW THERE ARE (4) MIAMI-DADE NOA 15-0820.06
 SUBMITTED NONE OF THE SCHEDULES ON THE 4 TECHNICAL
 SHEETS CIRCLED TO IDENTIFY WHICH SUB-SYSTEM, SIZE OF
 BRACKET/ UNIT, ANCHOR AND TYPE OF MATERIAL THE ANCHOR
 IS TO BE FASTEN. 107.2.1.3/ , 1609.6.4.4.1 COMPONENTS &
 CLADDING. RULE 61G-20-3.
 THERE IS A 2ND WHAT APPEARS TO BE A SHOP DRAWING FROM
 THE METAL SHOP, NOT A PRODUCT APPROVAL, NO COVER PAGE
 FOR A FLORIDA OR MIAMI-DADE NOA. 107.2.1.3/ ,
 1609.6.4.4.1 COMPONENTS & CLADDING. RULE 61G-20-3.
  
 1ST ROUND COMMENT. THE SUBMITTED MIAMI-DADE NOA
 15-0820.06 WAS SUBMITTED BUT NONE OF THE TABLES ON THE
 TECHNICAL SHEETS IDENTIFY THE UNIT SIZE / BRACKET, WALL
 TYPE, ANCHOR TYPE, MINIMUM EMBEDMENT, MINIMUM E. D.,
 RISK CATEGORY, BUILDING HEIGHT, ETC.? FBC-B 2014 FBC-B
 1604.4 ANALYSIS.
  
 3) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED.
  
 5) 2ND REQUEST. THE NEW ROLLING GARAGE DOOR IS SHOWN ON
 A-100 IN DETAIL 8. A SHOP DRAWING BY PEDRO FIGUEIREDO
 P. E. WAS SUBMITTED. IF THIS DOES NOT HAVE EITHER A
 FLORIDA APPROVAL OR A MIAMI-DADE NOA, A LOCAL APPROVAL
 CAN BE APPLIED FOR, THE CITY USES THE SAME CRITERIA AS
 THE STATE. . 107.2.1.3/ , 1609.6.4.4.1 COMPONENTS &
 CLADDING. RULE 61G-20-3.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1ST ROUND COMMENT. SHEET A-100 SHOWS THE ROLLING GARAGE
 DOOR AS EXISTING, THIS SAME PAGE SHOWS DETAIL W1 & S1
 FOR WINDOW AND SHUTTER, SHEET A-101 DETAIL 5 SHOWS
 PRESSURES FOR THIS OPENING, IS THIS PART OF THIS
 REVIEW, OR UNDER THE ORIGINAL BUILDING PERMIT?
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3.
  
 6) 2ND REQUEST. PLEASE NOTE THE COMMENT STANDS. PLEASE
 SEE THE DEFINITION OF A COMMERCIAL KITCHEN UNDER THE
 2014 FBC- MECHANICAL CODE. COMMERCIAL COOKING
 APPLIANCES. FOR THE PURPOSE OF THIS DEFINITION, A FOOD
 SERVICE ESTABLISHMENT SHALL INCLUDE ANY BUILDING OR A
 PORTION THEREOF USED FOR THE PREPARATION AND SERVING OF
 FOOD. APPLIANCES USED IN A COMMERCIAL FOOD SERVICE
 ESTABLISHMENT FOR HEATING OR COOKING FOOD AND WHICH
 PRODUCE GREASE VAPORS, STEAM, FUMES, SMOKE OR ODORS
 THAT ARE REQUIRED TO BE REMOVED THROUGH A LOCAL EXHAUST
 VENTILATION SYSTEM. SUCH APPLIANCES INCLUDE DEEP FAT
 FRYERS; UPRIGHT BROILERS; GRIDDLES; BROILERS;
 STEAM-JACKETED KETTLES; HOT-TOP RANGES; UNDER-FIRED
 BROILERS (CHARBROILERS); OVENS; BARBECUES; ROTISSERIES;
 AND SIMILAR APPLIANCES.
  
 1ST ROUND OF COMMENTS. SHEET A-101 DETAIL #9
 ILLUSTRATES THE USE OF A SLIDE IN RANGE, PLEASE PROVIDE
 COMPLIANCE WITH THE FBC-B SECTIONS:
 9.3.2.11.5 COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED IN COMMERCIAL
 KITCHEN EXHAUST HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC
 SPRINKLER SYSTEM IS USED TO COMPLY WITH SECTION 904.
 904.2 WHERE REQUIRED. AUTOMATIC FIRE-EXTINGUISHING
 SYSTEMS INSTALLED AS AN ALTERNATIVE TO THE REQUIRED
 AUTOMATIC SPRINKLER SYSTEMS OF SECTION 903 SHALL BE
 APPROVED BY THE FIRE CODE OFFICIAL. AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS SHALL NOT BE CONSIDERED
 ALTERNATIVES FOR THE PURPOSES OF EXCEPTIONS OR
 REDUCTIONS ALLOWED BY OTHER REQUIREMENTS OF THIS CODE.
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH REQUIRED
 COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEM
 REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR CHAPTER
 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO HAVE A
 TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 7) 2ND REQUEST. SHEET A-101 DETAIL #9 ILLUSTRATES THE
 USE OF A WALL OVEN, WHEN SCALED THE OPERATING KNOBS ARE
 LOCATED AT 4 FT. 9 INCHES ABOVE THE FINISH FLOOR OUT OF
 RANGE FOR REACH RANGES IN 308 OF THE ACCESSIBLITY CODE
 AND 309 OPERABLE PARTS.
  
 1ST ROUND OF COMMENT. SHEET A-101 DETAIL #9 ILLUSTRATES
 THE USE OF A WALL OVEN, PLEASE PROVIDE COMPLIANCE WITH
 THE ACCESS. CODE SECTIONS 308 FOR REACH RANGES AND 309
 FOR OPERABLE PARTS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  