Plan Review Notes
Plan Review Notes For Permit 17061260
Permit Number 17061260
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-13 18:11:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061260
 7/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 NEW TICKET BOOTH AND KITCHEN PER TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE
 THAT EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ.
 FT. IS REQUIRED FOR THE KITCHEN.
  
 2) PROVIDE AIR BALANCE CALCULATIONS FOR THE KITCHEN.
  
 3) PLACE A NOTE ON THE PLAN TO INDICATE SEPARATE
 PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST HOOD AND
 FIRE SUPPRESSION SYSTEM.
  