| Plan Review Notes For Permit 17061260 |
| Permit Number |
17061260 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-13 18:11:06 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061260 | | | 7/13/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | NEW TICKET BOOTH AND KITCHEN PER TABLE 403.3 FBC-14 | | | MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE | | | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE | | | THAT EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ. | | | FT. IS REQUIRED FOR THE KITCHEN. | | | | | | 2) PROVIDE AIR BALANCE CALCULATIONS FOR THE KITCHEN. | | | | | | 3) PLACE A NOTE ON THE PLAN TO INDICATE SEPARATE | | | PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST HOOD AND | | | FIRE SUPPRESSION SYSTEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|