| 2017-07-07 08:11:13 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17061260 |
| | ADD: 425 24TH ST. |
| | CONT: CLEAR SPAN STRUCTURES |
| | TEL: 561-803-8100 |
| | E-MAIL: MIACOBUCCICSSBUILDS.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 07/2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-100 AND A-101 BOTH INDICATE THE NEW LOCATION |
| | OF A ROOF TOP A/C CONDENSING UNIT. THE UNIT IS LOCATED |
| | ABOVE 16 FEET ABOVE GRADE. PLEASE PROVIDE COMPLIANCE |
| | WITH 2014 FBC-B SECTION: |
| | ? 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES HIGH OR WALKING ON ROOFS HAVING |
| | A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | 1.1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | 1.2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | 1.3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| | 6-INCHES (152 MM) DEEP. |
| | .4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | 1.5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | 1.6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| | 1.7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| | REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| | MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| | SERVICE PLATFORMS. |
| | |
| | 2) THE SUBMITTED MIAMI-DADE NOA 15-0820.06 WAS |
| | SUBMITTED BUT NONE OF THE TABLES ON THE TECHNICAL |
| | SHEETS IDENTIFY THE UNIT SIZE / BRACKET, WALL TYPE, |
| | ANCHOR TYPE, MINIMUM EMBEDMENT, MINIMUM E. D., RISK |
| | CATEGORY, BUILDING HEIGHT, ETC.? FBC-B 2014 FBC-B |
| | 1604.4 ANALYSIS. |
| | |
| | 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) SHEET A-101 SHOWS THE TICKET BOOTH TOWER AT A HIGHER |
| | FINISH ROOF ELEVATION THAN THE SURROUNDING PARAPET |
| | WALLS. IT APPEARS THAT THE PARAPET WALLS WILL REQUIRE |
| | GUARD RAILS IN COMPLIANCE WITH FBC-B 1013.7. |
| | |
| | 5) SHEET A-100 SHOWS THE ROLLING GARAGE DOOR AS |
| | EXISTING, THIS SAME PAGE SHOWS DETAIL W1 & S1 FOR |
| | WINDOW AND SHUTTER, SHEET A-101 DETAIL 5 SHOWS |
| | PRESSURES FOR THIS OPENING, IS THIS PART OF THIS |
| | REVIEW, OR UNDER THE ORIGINAL BUILDING PERMIT? |
| | ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3. |
| | |
| | 6) SHEET A-101 DETAIL #9 ILLUSTRATES THE USE OF A SLIDE |
| | IN RANGE, PLEASE PROVIDE COMPLIANCE WITH THE FBC-B |
| | SECTIONS: |
| | 9.3.2.11.5 COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE INSTALLED IN COMMERCIAL |
| | KITCHEN EXHAUST HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC |
| | SPRINKLER SYSTEM IS USED TO COMPLY WITH SECTION 904. |
| | 904.2 WHERE REQUIRED. AUTOMATIC FIRE-EXTINGUISHING |
| | SYSTEMS INSTALLED AS AN ALTERNATIVE TO THE REQUIRED |
| | AUTOMATIC SPRINKLER SYSTEMS OF SECTION 903 SHALL BE |
| | APPROVED BY THE FIRE CODE OFFICIAL. AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS SHALL NOT BE CONSIDERED |
| | ALTERNATIVES FOR THE PURPOSES OF EXCEPTIONS OR |
| | REDUCTIONS ALLOWED BY OTHER REQUIREMENTS OF THIS CODE. |
| | |
| | 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH REQUIRED |
| | COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEM |
| | REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR CHAPTER |
| | 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO HAVE A |
| | TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN |
| | ACCORDANCE WITH THIS CODE. |
| | |
| | 7) SHEET A-101 DETAIL #9 ILLUSTRATES THE USE OF A WALL |
| | OVEN, PLEASE PROVIDE COMPLIANCE WITH THE ACCESS. CODE |
| | SECTIONS 308 FOR REACH RANGES AND 309 FOR OPERABLE |
| | PARTS. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |