Plan Review Notes
Plan Review Notes For Permit 17061243
Permit Number 17061243
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-28 08:22:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
  
 1. FBC 107 SCOPE NOT CLEAR.
  
 THERE IS AN OPEN MECHANICAL PERMIT, 17050350 WHICH
 APPLICATION STATES IS THE MASTER; PLAN STATES IN NOTE
 1:
  
 TOP OF EXISTING 2X10 EL=119.67
  
 THERE IS A ROOF PERMIT ASSOCIATED WITH THAT MECHANICAL
 PERMIT.
  
 IF THIS ROOF ARE IS UNRELATED TO PERMIT 17050350,
 PLEASE ADVISE AS TO STATUS OF MECHANICAL PERMIT FOR
 THIS ROOF WORK.
  
 2. THE VALUE OF PERMIT 17050350 APPEARS TOO LOW TO
 INCLUDE THIS PERMIT; CLARIFY SCOPE, CONTRACT MAY BE
 REQUIRED, FBC 109.
  
 3. IF ASSOCIATED WITH THE MASTER 17050350, THE
 STRUCTURAL ENGINEER OF RECORD IS TO SPECIFY DESIGN
 PRESSURES FOR COMPONENTS & CLADDING AND IS TO REVIEW
 THE SUBMITTAL.
  
 4. IF ASSOCIATED WITH THE MASTER 17050350, EXPLAIN WHY
 THERE IS AN OPEN ROOF PERMIT ASSOCIATED WITH THAT
 PERMIT. THE SCOPE OF THIS PROJECT APPEARS TOO SMALL TO
 HAVE TWO DIFFERENT ROOFING CONTRACTORS ON THE SAME JOB,
 FBC 107.
  
 5. IF ASSOCIATED WITH THE MASTER 17050350, A BUILDING
 PERMIT OR A REVISION IS REQUIRED. THE PLAN SPECIFIES
 STRUCTURAL WORK; THIS IS NOT WITHIN THE SCOPE OF A
 MECHANICAL OR A ROOFING CONTRACTOR LICENSE.