| Plan Review Notes For Permit 17061243 |
| Permit Number |
17061243 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-28 08:22:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | | | | 1. FBC 107 SCOPE NOT CLEAR. | | | | | | THERE IS AN OPEN MECHANICAL PERMIT, 17050350 WHICH | | | APPLICATION STATES IS THE MASTER; PLAN STATES IN NOTE | | | 1: | | | | | | TOP OF EXISTING 2X10 EL=119.67 | | | | | | THERE IS A ROOF PERMIT ASSOCIATED WITH THAT MECHANICAL | | | PERMIT. | | | | | | IF THIS ROOF ARE IS UNRELATED TO PERMIT 17050350, | | | PLEASE ADVISE AS TO STATUS OF MECHANICAL PERMIT FOR | | | THIS ROOF WORK. | | | | | | 2. THE VALUE OF PERMIT 17050350 APPEARS TOO LOW TO | | | INCLUDE THIS PERMIT; CLARIFY SCOPE, CONTRACT MAY BE | | | REQUIRED, FBC 109. | | | | | | 3. IF ASSOCIATED WITH THE MASTER 17050350, THE | | | STRUCTURAL ENGINEER OF RECORD IS TO SPECIFY DESIGN | | | PRESSURES FOR COMPONENTS & CLADDING AND IS TO REVIEW | | | THE SUBMITTAL. | | | | | | 4. IF ASSOCIATED WITH THE MASTER 17050350, EXPLAIN WHY | | | THERE IS AN OPEN ROOF PERMIT ASSOCIATED WITH THAT | | | PERMIT. THE SCOPE OF THIS PROJECT APPEARS TOO SMALL TO | | | HAVE TWO DIFFERENT ROOFING CONTRACTORS ON THE SAME JOB, | | | FBC 107. | | | | | | 5. IF ASSOCIATED WITH THE MASTER 17050350, A BUILDING | | | PERMIT OR A REVISION IS REQUIRED. THE PLAN SPECIFIES | | | STRUCTURAL WORK; THIS IS NOT WITHIN THE SCOPE OF A | | | MECHANICAL OR A ROOFING CONTRACTOR LICENSE. |
|