2017-06-29 10:53:521ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SIZING TABLE FOR CSST PIPING. PER WPB AMEND
 TO FBC 107.2.1
  
 2. PLEASE PROVIDE EHD # ON RISER FOR CSST PIPE. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PROVIDE LONGEST RUN LENGTH FOR .5LB SYSTEM. PER FBC
 FG 402.4.1
  
 4. THE WAY THE RISER AND FLAT DRAWING ARE DRAWN IT
 SHOWS THE PE PIPING RUNNING UNDER THE BUILDING WHICH IS
 NOT ALLOWED PLEASE SHOW TRANSITION FROM PE TO GALV OR
 CSST BEFORE ENTERING BUILDING. PER FBC FG 404.17.1
  
 5. PLANS SHALL BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL OF RECORD. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  