| Plan Review Notes For Permit 17061233 |
| Permit Number |
17061233 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-29 11:09:30 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SPECIFY A 90 LB HOT MOP ON 30 LB FELT | | | ROOFING SYSTEM. THE PRODUCT APPROVAL THAT WAS SUBMITTED | | | IS FOR A SBS SELF ADHERED ROOFING SYSTEM. SUBMIT | | | PRODUCT APPROVALS FOR THE SYSTEM SPECIFIED ON THE PLANS | | | OR A SIGNED AND SEALED LETTER FROM THE ARCHITECT, | | | BERNARD JONES, REVISING THE ROOF COVERING SYSTEM. FBC | | | 107.2.1 | | | | | | 2) THE SELF ADHERED SBS ROOFING SYSTEM (W-138 FROM | | | FL1654) HAS A MAXIMUM DESIGN UPLIFT PRESSURE OF - 90 | | | PSF. THE STRUCTURE HAS A 12' MRH AND IS LOCATED IN | | | EXPOSURE C WITH A 170 MPH VULT WINDSPEED. ROOF ZONE 3 | | | (CORNERS) REQUIRES AN UPLFT PRESSURE OF -95.7 PSF. THE | | | SELECTED PRODUCT IS NOT ACCEPTABLE. FBC-R301.1 |
|