| Plan Review Notes For Permit 17061232 |
| Permit Number |
17061232 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-29 10:19:32 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SPECIFY A TPO (THERMOPLASTIC POLYOLEFIN) | | | ROOF COVERING. THE PRODUCT APPROVAL THAT WAS SUBMITTED | | | IS FOR A SBS (MODIFIED ASPHALT) ROOF COVERING. SUBMIT | | | PRODUCT APPROVALS FOR THE TPO ROOFING OR PROVIDE A | | | SIGNED AND SEALED LETTER FROM THE ARCHITECT, EUGENE R. | | | FAGAN III, REVISING THE ROOF COVERING. FBC 107.2.1 | | | | | | 2) THE PLANS SPECIFY THE REQUIRED ROOF DESIGN PRESSURES | | | OF +36, -101 PSF FOR ROOF ZONE 2 AND +36, -149 PSF FOR | | | ROOF ZONE 3. THE MAXIMUM DESIGN PRESSURE FOR THE SBS | | | SELF ADHERED SYSTEM (W-138 FROM FL1654) THAT WAS | | | SUBMITTED IS -90 PSF, WHICH IS TOO LOW. FBC-R301.1 | | | | | | |
|