| Date |
Text |
| 2017-07-17 09:10:18 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. SHOW COMPLIANCE WITH ENERGY CODE FOR LIGHTING: "A |
| | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1 |
| | 2. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUITS 15, 24, |
| | SHOULD BE AFCI PROTECTED CIRCUITS. CIRCUIT 29 SHOWS A |
| | #14 WIRE ON A 20 AMP BREAKER. NEC 215.5, 408.4, ; FBC |
| | 107.2.1, FBC RE3706.1 |
| | 3. WIRE FEEDING INTERIOR PANEL FROM OUTSIDE SERVICE IS |
| | TOO SMALL. 2/0 COPPER CAN ONLY BE USED WHERE IT FEEDS |
| | 100% OF THE LOAD. PROVIDE CORRECTION. NEC 310.15(B)(7); |
| | FBC RE3602.2 |
| | 4. KITCHEN COUNTER OUTLETS SHOW ONLY ONE CIRCUIT (#20). |
| | CODE REQUIRES MINIMUM OF 2 SMALL APPLIANCE CIRCUITS. |
| | PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(3); FBC |
| | RE3703.2 |
| | 5. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE |
| | CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER |
| | CODE. PROVIDE CORRECTION. NEC 210.11(C)(1), |
| | 210.52(B)(2),(3); FBC RE3703.2 |
| | 6. LOAD CALCULATION SHOULD INCLUDE 2 SMALL APPLIANCE |
| | CIRCUITS. NEC 210.11(C)(1), NEC 220,; FBC RE3602.2 |
| | 7. IN SEVERAL LOCATIONS THE OUTLET SPACING IS NOT |
| | WITHIN THE LIMITS PER CODE: "RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET". PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE3901.2.1 |
| | 8. PROVIDE NOTE TO COMPLY WITH CODE FOR LIGHTING IN |
| | CLOSETS PER NEC 410.16, FBC RE4003.12. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |