| 2017-07-03 11:05:13 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. 1551 N. FLAGLER IS CONSTRUCTED WITH A SIX INCH THICK |
| | POST TENSIONED ELEVATED SLAB. |
| | 2. THE REVISION SUBMITTED HAS TWO DIFFERENT PROPOSED |
| | UNDERLAYMENTS. |
| | 2A. ASTM 492 (IMPACT) TEST REPORT FOR LATICRETE 125 FOR |
| | A 6 INCH SLAB. |
| | 2B. ASTM 492 (IMPACT) & ASTM 90 (AIRBOURNE) FOR PROFLEX |
| | RCU-250 FOR AN 8 INCH SLAB. |
| | 3. PROVIDE A COPY OF TEST REPORTS 492 & 90 FOR AN |
| | UNDERLAYMENT INSTALLED ON A 6 INCH SLAB FOR CERAMIC |
| | TILE. |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | |