| Plan Review Notes For Permit 17061198 |
| Permit Number |
17061198 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-09-26 11:30:34 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061198 | | | 9/26/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE RESUBMITTED AC CALCULATIONS FOR ZONE 1 AND ZONE | | | 2 ARE IDENTICAL WHICH INDICATES ONE WAS COPIED FROM THE | | | OTHER. PLEASE SUBMIT ORIGINAL CALCULATIONS FOR EACH | | | ZONE. | | | | | | 2) THE RESUBMITTED AC CALCULATIONS SHOW AHRI REFERENCE | | | NUMBERS THAT DO NOT MATCH THE CERTIFICATES SUBMITTED. | | | | | | 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT SPEC SHEETS | | | FOR THE RANGE HOODS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|