Plan Review Notes
Plan Review Notes For Permit 17061198
Permit Number 17061198
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-16 18:07:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061198
 8/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I
 AM REPRINTING THEM BELOW WITH ADDITIONAL COMMENTS AND
 CLARIFICATIONS. PLEASE COMPLY.
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061198
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC
 CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS
 TO BE FACING EAST ACCORDING TO AERIAL MAPS- SEE SECTION
 312.1
  
 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION
 SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2.
 (CERTIFICATE FOR AC# 3 SUBMTTED, BUT CERTIFICATES FOR
 AC #1 & 2 SYSTEMS NOT SUBMITTED.)
  
 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND
 AHU-1 IN THE NEW CLOSET- SECTION 603.1.1.
  
 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT
 THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2
 THE DOOR SHALL BE NON-COMBUSTIBLE. (IN OTHER WORDS A
 PLENUM-RATED METAL DOOR MUST BE INSTALLED BECAUSE THIS
 IS NOT A SINGLE-FAMILY HOME. IT IS REGULATED BY THE
 COMMERCIAL CODE).
  
 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW
 KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE
 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE
 BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS-
 SECTION 505. (PLEASE NOTE THE SPECS FOR THE RANGE HOODS
 WERE NOT SUBMIITED).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  