| 2017-08-16 18:07:33 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17061198 |
| | 8/16/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I |
| | AM REPRINTING THEM BELOW WITH ADDITIONAL COMMENTS AND |
| | CLARIFICATIONS. PLEASE COMPLY. |
| | |
| | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17061198 |
| | 7/21/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC |
| | CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS |
| | TO BE FACING EAST ACCORDING TO AERIAL MAPS- SEE SECTION |
| | 312.1 |
| | |
| | 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION |
| | SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2. |
| | (CERTIFICATE FOR AC# 3 SUBMTTED, BUT CERTIFICATES FOR |
| | AC #1 & 2 SYSTEMS NOT SUBMITTED.) |
| | |
| | 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND |
| | AHU-1 IN THE NEW CLOSET- SECTION 603.1.1. |
| | |
| | 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT |
| | THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2 |
| | THE DOOR SHALL BE NON-COMBUSTIBLE. (IN OTHER WORDS A |
| | PLENUM-RATED METAL DOOR MUST BE INSTALLED BECAUSE THIS |
| | IS NOT A SINGLE-FAMILY HOME. IT IS REGULATED BY THE |
| | COMMERCIAL CODE). |
| | |
| | 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW |
| | KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE |
| | 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE |
| | BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS- |
| | SECTION 505. (PLEASE NOTE THE SPECS FOR THE RANGE HOODS |
| | WERE NOT SUBMIITED). |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |