2017-08-14 10:24:39CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE REQUIRED
 EQUIPMENT GROUNDING CONDUCTOR TO THE INTERIOR PANELS.
 ADDITIONALLY, THE INTERSYSTEM BONDING TERMINATION POINT
 IS NOT SHOWN. PROVIDE CORRECTION. NEC 250.122, 250.94
 2. PLAN PROVIDED SHOWS ONE OF THE METERS BEING
 RELOCATED TO THE REAR BUILDING. ONLY ONE SERVICE, WITH
 A MAXIMUM OF SIX DISCONNECTS, IS PERMITTED PER CODE.
 ADDITIONALLY, FPL ELECTRIC SERVICE STANDARDS STATE THAT
 ONLY ONE SERVICE DROP IS PROVIDED PER LOT. RISER
 DIAGRAM NEEDS TO BE REVISED TO SHOW ALL METERS AT THE
 SAME LOCATION, FED FROM A SINGLE SERVICE. LOAD
 CALCULATION FOR THIS SERVICE SHOULD BE PROVIDED AS
 PREVIOUSLY REQUESTED TO CONFIRM THE SERVICE SIZE IS
 ADEQUATE. MORE DETAIL SHOULD BE PROVIDED IN REFERENCE
 TO THE SERVICE CONDUCTORS IN THE RISER. WILL THERE BE 2
 SETS OF THREE 4/0 AL? PLEASE CLARIFY. NEC 230.2,
 230.71, 310.15(B)(7), FBC 107.2.1
 3. 1ST FLOOR ELECTRICAL PLAN SHOWS ONE OF THE PANELS
 LOCATED IN WHAT APPEARS TO BE THE BATHROOM AREA.
 OVERCURRENT PROTECTION DEVICES ARE NOT PERMITTED IN
 BATHROOMS. PROVIDE CORRECTION. NEC 240.24(E)
 4. ONLY ONE PANEL SCHEDULE WAS PROVIDED. PROVIDE
 SCHEDULE FOR EACH PANEL WITH THE APPROPRIATE NAME FOR
 THAT PANEL. BREAKER FOR WATER HEATER SHOULD BE A 25 AMP
 BREAKER, BASED ON THE LOAD. NEC 215.5, 408.4, 422.13,
 FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  