| 2017-08-14 10:24:39 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE REQUIRED |
| | EQUIPMENT GROUNDING CONDUCTOR TO THE INTERIOR PANELS. |
| | ADDITIONALLY, THE INTERSYSTEM BONDING TERMINATION POINT |
| | IS NOT SHOWN. PROVIDE CORRECTION. NEC 250.122, 250.94 |
| | 2. PLAN PROVIDED SHOWS ONE OF THE METERS BEING |
| | RELOCATED TO THE REAR BUILDING. ONLY ONE SERVICE, WITH |
| | A MAXIMUM OF SIX DISCONNECTS, IS PERMITTED PER CODE. |
| | ADDITIONALLY, FPL ELECTRIC SERVICE STANDARDS STATE THAT |
| | ONLY ONE SERVICE DROP IS PROVIDED PER LOT. RISER |
| | DIAGRAM NEEDS TO BE REVISED TO SHOW ALL METERS AT THE |
| | SAME LOCATION, FED FROM A SINGLE SERVICE. LOAD |
| | CALCULATION FOR THIS SERVICE SHOULD BE PROVIDED AS |
| | PREVIOUSLY REQUESTED TO CONFIRM THE SERVICE SIZE IS |
| | ADEQUATE. MORE DETAIL SHOULD BE PROVIDED IN REFERENCE |
| | TO THE SERVICE CONDUCTORS IN THE RISER. WILL THERE BE 2 |
| | SETS OF THREE 4/0 AL? PLEASE CLARIFY. NEC 230.2, |
| | 230.71, 310.15(B)(7), FBC 107.2.1 |
| | 3. 1ST FLOOR ELECTRICAL PLAN SHOWS ONE OF THE PANELS |
| | LOCATED IN WHAT APPEARS TO BE THE BATHROOM AREA. |
| | OVERCURRENT PROTECTION DEVICES ARE NOT PERMITTED IN |
| | BATHROOMS. PROVIDE CORRECTION. NEC 240.24(E) |
| | 4. ONLY ONE PANEL SCHEDULE WAS PROVIDED. PROVIDE |
| | SCHEDULE FOR EACH PANEL WITH THE APPROPRIATE NAME FOR |
| | THAT PANEL. BREAKER FOR WATER HEATER SHOULD BE A 25 AMP |
| | BREAKER, BASED ON THE LOAD. NEC 215.5, 408.4, 422.13, |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |