2017-07-11 18:56:531ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW SHOWER AND WATER CLOSET ON FIRST FLOOR ARE
 NOT VENTED. FBC RES P3101.2.1
  
 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC RES P3005.2.6
  
 3. THE TWOWAY CLEAN OUT AT THE SEWER IS UNDER SIZED.
 CLEANOUTS SHALL BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102 MM). FOR PIPES LARGER
 THAN 4 INCHES (102 MM) NOMINAL SIZE, THE SIZE OF THE
 CLEANOUT SHALL BE NOT LESS THAN 4 INCHES (102 MM). PER
 FBC RES P3005.2.9
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  