| 2017-07-21 16:17:52 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17061198 |
| | 7/21/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC |
| | CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS |
| | TO BE FACING EITHER NORTH OR EAST ACCORDING TO AERIAL |
| | MAPS- SEE SECTION 312.1 |
| | |
| | 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION |
| | SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2. |
| | |
| | 3) PLEASE CLARIFY THE SCOPE OF WORK FOR MECHANICAL ON |
| | THE PROJECT: SHEET 1.1 INDICATES EXISTING DUCTS AND |
| | DIFFUSERS, BUT SHEET 4.1 APPEARS TO INDICATE NEW DUCTS, |
| | DIFFUSERS, AND RETURN TRANSFERS ALONG WITH NEW AC |
| | SYSTEMS. |
| | |
| | 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND |
| | AHU-1 IN THE NEW CLOSET- SECTION 603.1.1. |
| | |
| | 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT |
| | THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2 |
| | THE DOOR SHALL BE NON-COMBUSTIBLE. |
| | |
| | 6) 4.1: CLARIFY HOW THE 6" DUCT IS RUNNING THROUGH THE |
| | LIVING ROOM TO THE SITTING ROOM ON THE NORTH SIDE. ALL |
| | OTHER DUCTS ARE IN SOFFITS. |
| | |
| | 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW |
| | KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE |
| | 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE |
| | BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS- |
| | SECTION 505. |
| | |
| | 8) 4.1: PLEASE LABEL THE BATH EXHAUST FANS CORRECTLY IN |
| | THE LEGEND. |
| | |
| | 9) 4.1: CLARIFY IF NEW CLOTHES DRYERS WILL BE INSTALLED |
| | IN THE APARTMENTS. SHOW THEIR LOCATIONS AND PROVIDE |
| | EXHAUST VENTING PLANS IF APPLICABLE. |
| | |
| | CHRISTOPHER L. COLE |