Plan Review Notes
Plan Review Notes For Permit 17061198
Permit Number 17061198
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-10 14:51:18CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE COMPLETE RISER DIAGRAM WITH DETAILS OF ALL
 CONDUCTOR SIZES AND THE GROUNDING ELECTRODE SYSTEM. NEC
 215.5, 250.50
 2. PROVIDE OUTLETS SPACES AS REQUIRED PER NEC. NEC
 210.52
 3. SHOW LOCATION OF ALL SMOKE ALARMS. IF NONE ARE
 EXISTING, OR ARE NOT TO CODE, SHOW AS NEW INSTALLATION
 WITH AFCI PROTECTION. FBC 907.2.11; NEC 210.12
 4. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE
 ALL LOADS FROM BOTH BUILDINGS TO DETERMINE THAT SERVICE
 IS SUFFICIENTLY SIZED. NEC 220
 5. PROVIDE AFCI PROTECTION FOR ANY NEW OR ALTERED
 CIRCUITS. NEC 210.12(B)
 6. SHOW LOCATION OF ANY EXISTING ELECTRICAL PANELS. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  