| Plan Review Notes For Permit 17061198 |
| Permit Number |
17061198 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-10 14:51:18 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. PROVIDE COMPLETE RISER DIAGRAM WITH DETAILS OF ALL | | | CONDUCTOR SIZES AND THE GROUNDING ELECTRODE SYSTEM. NEC | | | 215.5, 250.50 | | | 2. PROVIDE OUTLETS SPACES AS REQUIRED PER NEC. NEC | | | 210.52 | | | 3. SHOW LOCATION OF ALL SMOKE ALARMS. IF NONE ARE | | | EXISTING, OR ARE NOT TO CODE, SHOW AS NEW INSTALLATION | | | WITH AFCI PROTECTION. FBC 907.2.11; NEC 210.12 | | | 4. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE | | | ALL LOADS FROM BOTH BUILDINGS TO DETERMINE THAT SERVICE | | | IS SUFFICIENTLY SIZED. NEC 220 | | | 5. PROVIDE AFCI PROTECTION FOR ANY NEW OR ALTERED | | | CIRCUITS. NEC 210.12(B) | | | 6. SHOW LOCATION OF ANY EXISTING ELECTRICAL PANELS. FBC | | | 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|