| Plan Review Notes For Permit 17061198 |
| Permit Number |
17061198 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-21 14:40:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THIS STRUCTURE HAS THREE SEPARATE LIVING SPACES EACH | | | ONE HAS A KITCHEN. THEREFORE, IT IS NOT CONSIDERED A | | | SINGLE FAMILY RESIDENCE (R3). THE FBC BUILDING WILL | | | APPLY RATHER THAN THE FBC RESIDENTIAL. PLEASE REVISE | | | THE GENERAL NOTES, DESIGN PARAMETERS AND REFERENCED | | | CODES ON SHEET A2.1. FBC SECTION 310 | | | | | | 2) THE AREA TABULATIONS ON SHEETS A1.1 AND A2.1 ARE | | | INCORRECT. THE EXISTING TOTAL UNDER ROOF SHOULD BE 2963 | | | SQFT., PLEASE CORRECT. FBC 107.2.1 | | | | | | 3) PLEASE NOTE: THIS HOUSE IS A DESIGNATED HISTORIC | | | STRUCTURE AND IS EXEMPT FROM THE FBC ENERGY | | | CONSERVATION REQUIREMENTS. HOWEVER, THE HEATING AND | | | COOLING SYSTEM DESIGN LOAD CALCULATIONS FOR SIZING THE | | | EQUIPMENT ARE REQUIRED PER FBC MECHANICAL SECTION | | | 312.1. | | | |
|