2017-08-18 13:58:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORMS R405-2014. FBC ENERGY CONSERVATION
 R103.1.1.2
  
 2) CLARIFY HOW THE PENETRATIONS OF THE FIRE RATED
 CEILING/FLOOR ASSEMBLY FOR THE MECHANICAL DUCT WORK AND
 ELECTRICAL CEILING FIXTURES WILL ADDRESSED. R302.4
 DWELLING UNIT RATED PENETRATIONS. PENETRATIONS OF WALL
 OR FLOOR/CEILING ASSEMBLIES REQUIRED TO BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH SECTION R302.2
 OR R302.3 SHALL BE PROTECTED IN ACCORDANCE WITH THIS
 SECTION.
  
  
  
  
  