| 2017-07-10 13:50:59 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. ONLY ONE SERVICE IS PERMITTED. CURRENTLY, THE |
| | SERVICE FOR THE DOWNSTAIRS IS LOCATED ON THE MAIN |
| | HOUSE. IT IS NOT PERMISSIBLE TO ADD AN ADDITIONAL |
| | SERVICE FED FROM A DIFFERENT LOCATION. PROVIDE LOAD |
| | CALCULATION FOR ENTIRE SERVICE SHOWING REQUIRED SERVICE |
| | SIZE. NEC 230.2, 220 |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE AND GROUNDING ELECTRODE SYSTEM. NEC 215.5, |
| | 250.50 |
| | 2. PROVIDE SERVICE DISCONNECT FOR EACH PANEL. NEC |
| | 230.70 |
| | 3. WIRE SIZE SHOWN TO UPSTAIRS PANEL IS #3 CU, WHICH IS |
| | NOT RATED FOR 125 AMPS. PROVIDE CORRECTION. NEC |
| | 310.15(B)(7), 310.15(B)(16) |
| | 4. INDICATE CIRCUIT FOR SMOKE ALARMS INSTALLED, PROVIDE |
| | AFCI PROTECTION AND INTERCONNECTION AS REQUIRED. FBC |
| | R314; FBC 107.3.5, 107.2.1; NEC 210.12 |
| | 5. THERE IS A NOTE THAT STATES TAMPER RESISTANT OUTLETS |
| | ARE REQUIRED PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT OUTLETS. PROVIDE CORRECTION. |
| | NEC 406.12; FBC 107.2.1 |
| | 6. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS. PROVIDE NOTE TO COMPLY. |
| | NEC 410.16 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |