Plan Review Notes
Plan Review Notes For Permit 17061197
Permit Number 17061197
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-10 13:50:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ONLY ONE SERVICE IS PERMITTED. CURRENTLY, THE
 SERVICE FOR THE DOWNSTAIRS IS LOCATED ON THE MAIN
 HOUSE. IT IS NOT PERMISSIBLE TO ADD AN ADDITIONAL
 SERVICE FED FROM A DIFFERENT LOCATION. PROVIDE LOAD
 CALCULATION FOR ENTIRE SERVICE SHOWING REQUIRED SERVICE
 SIZE. NEC 230.2, 220
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE AND GROUNDING ELECTRODE SYSTEM. NEC 215.5,
 250.50
 2. PROVIDE SERVICE DISCONNECT FOR EACH PANEL. NEC
 230.70
 3. WIRE SIZE SHOWN TO UPSTAIRS PANEL IS #3 CU, WHICH IS
 NOT RATED FOR 125 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(7), 310.15(B)(16)
 4. INDICATE CIRCUIT FOR SMOKE ALARMS INSTALLED, PROVIDE
 AFCI PROTECTION AND INTERCONNECTION AS REQUIRED. FBC
 R314; FBC 107.3.5, 107.2.1; NEC 210.12
 5. THERE IS A NOTE THAT STATES TAMPER RESISTANT OUTLETS
 ARE REQUIRED PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT OUTLETS. PROVIDE CORRECTION.
 NEC 406.12; FBC 107.2.1
 6. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE NOTE TO COMPLY.
 NEC 410.16
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  