| 2017-07-20 16:35:06 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY FORMS R405-2014. FBC ENERGY CONSERVATION |
| | R103.1.1.2 |
| | |
| | 2) THE EXISTING AREA TABULATION TABLES ON THE PLANS ARE |
| | INCORRECT. THE GARAGE/STORAGE SPACE ON THE FIRST FLOOR |
| | SHOULD NOT BE INCLUDED IN THE EXISTING LIVING AREA. FBC |
| | 107.2.1 |
| | |
| | 3) SHOW THAT THE GARAGE/STORAGE AREA WILL COMPLY WITH |
| | THE FOLLOWING: FBC - R302.3 TWO-FAMILY DWELLINGS. |
| | DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE |
| | SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR |
| | ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR |
| | FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND |
| | BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES |
| | SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF |
| | THE ROOF SHEATHING. R302.3.1 SUPPORTING CONSTRUCTION. |
| | WHEN FLOOR ASSEMBLIES ARE REQUIRED TO BE |
| | FIRE-RESISTANCE RATED BY SECTION R302.3, THE SUPPORTING |
| | CONSTRUCTION OF SUCH ASSEMBLIES SHALL HAVE AN EQUAL OR |
| | GREATER FIRE-RESISTANCE RATING. R302.4 DWELLING UNIT |
| | RATED PENETRATIONS. PENETRATIONS OF WALL OR |
| | FLOOR/CEILING ASSEMBLIES REQUIRED TO BE FIRE-RESISTANCE |
| | RATED IN ACCORDANCE WITH SECTION R302.2 OR R302.3 SHALL |
| | BE PROTECTED IN ACCORDANCE WITH THIS SECTION. |
| | |
| | |
| | |