Plan Review Notes
Plan Review Notes For Permit 17061161
Permit Number 17061161
Review Stop G
Sequence Number 2
Notes
Date Text
2017-07-13 14:59:441) WHAT IS THE GAS LINE CONNECTING TO IN THE UTILITY
 EASEMENT? IS THE GAS LINE IN THE EASEMENT A PUBLIC
 UTILITY LINE? IF SO, A PLUMBING CONTRACTOR CANNOT DO
 THIS SCOPE OF WORK. IT IS UNDER THE AUTHORITY OF THE
 PUBLIC SERVICE COMMISSION AND THE GAS PURVEYOR.
 CLARIFY.FL. STATUTE 489.105.
 2) THE SCOPE OF WORK ON THE APPLICATION NOTES A
 CONNECTION TO AN EXISTING GAS METER. IF THERE IS AN
 EXISTING GAS METER THERE SHOULD BE AN EXISTING SERVICE
 LINE CONNECTION TO THIS METER.CLARIFY WHY THIS LINE IS
 BEING REPLACED.
 3) THE SUBMITTED PLAN IS SO DEFICIENT IN THE REQUIRED
 INFORMATION A COMPREHENSIVE REVIEW COULD NOT BE
 ACCOMPLISHED. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED AND
 PIPE SIZE.WPB AMENDMENTS TO FBC SEC.107.2.1.
 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 NOTE: THE ADDITIONAL DOCUMENTS YOU HAVE SUBMITTED FOR
 REVIEW ARE NO BETTER THAN WHAT WAS ORIGINALLY
 SUBMITTED. COMPLY WITH ALL PREVIOUS PLAN REVIEW
 COMMENTS. I SUGGEST YOU CONTACT THIS REVIEWER TO SET UP
 AN APPOINTMENT TO DISCUSS THESE COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  