Plan Review Notes
Plan Review Notes For Permit 17061148
Permit Number 17061148
Review Stop R
Sequence Number 2
Notes
Date Text
2017-10-12 13:01:041- FLAT ROOF NOA 14-0529.02 SUBMITTED: THE DESIGN
 PRESSURE OF SELECTED ASSEMBLY ON PAGE 26 OF 42 DOESN'T
 MEET THE DESIGN PRESSURE FOR ALL ROOF ZONES. PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA. NEED
 THE CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT.