| Notes |
| Date |
Text |
| 2017-10-12 13:01:04 | 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: THE DESIGN | | | PRESSURE OF SELECTED ASSEMBLY ON PAGE 26 OF 42 DOESN'T | | | MEET THE DESIGN PRESSURE FOR ALL ROOF ZONES. PROVIDE | | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL | | | ENHANCING AT THE PERIMETER AND CORNER AREAS AS REQUIRED | | | BY GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA. NEED | | | THE CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. | | | R301.1 FBC-RESIDENTIAL. | | | REPEAT COMMENT. |
|