2017-10-17 11:15:08CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS CORRECTED ARE NOTED, THE
 REMAINING ITEMS NEED FURTHER CORRECTION. EXPLANATION IN
 (PARENTHESES):
  
 1. BASED ON THE LOAD CALCULATION PROVIDED, THE EXISTING
 SERVICE IS TOO SMALL TO ACCOMMODATE THE LOAD. PROVIDE
 CORRECTION. NEC 215.2, 220, FBC RE3602.1 (THE LAUNDRY
 CIRCUIT MUST BE CALCULATED AT 1500 VA. ALTHOUGH THIS
 DOESN'T CHANGE THE SERVICE SIZE, PROVIDE CORRECTION SO
 RECORDS ARE CORRECT.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. PROVIDE PANEL SCHEDULE/SIZING FOR ALL PANELS.
 INDICATE ANY NEW OR ALTERED CIRCUITS, AFCI OR GFCI
 PROTECTION AS REQUIRED. NEC 215.5, 408.4, 408.30 FBC
 RE3706.1 (PANEL SP SHOWS THE WATER HEATER ON A 30 AMP
 BREAKER. BASED ON 125% OF THE LOAD, THIS BREAKER SHOULD
 BE A 25 AMP. PROVIDE CORRECTION. ALSO, THE NEW PANEL SP
 DOES NOT INDICATE AFCI OR GFCI AS REQUESTED. A NOTE
 WILL SUFFICE, STATING: "ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12")
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE DETAILS OF SAUNA. DOES THIS REQUIRE GFCI
 PROTECTION? NEC 110.3; FBC 107.2.1 (DETAILS AND/OR SPEC
 SHEETS NOT PROVIDED, AND THERE IS CONFLICTING
 INFORMATION ON PLAN. THERE IS A STATEMENT ON PLAN THAT
 "SAUNA DOES NOT REQUIRE POWER, CONTROLS ARE BATTERY
 POWERED". HOWEVER, THE PANEL SCHEDULE SHOWS A 30 AMP
 CIRCUIT WITH A 5300 VA LOAD FOR THE SAUNA. PROVIDE
 PREVIOUSLY REQUESTED INFORMATION AND CORRECT PLAN.)
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL. FS 471, FAC61G15-23, FBC 107.3.5 (ONE SET
 OF PLANS STILL HAS THE OLD ELECTRICAL DRAWING. BOTH
 SETS NEED THE CORRECTED DRAWING, SIGNED AND SEALED.)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER