| 2017-10-17 11:15:08 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS CORRECTED ARE NOTED, THE |
| | REMAINING ITEMS NEED FURTHER CORRECTION. EXPLANATION IN |
| | (PARENTHESES): |
| | |
| | 1. BASED ON THE LOAD CALCULATION PROVIDED, THE EXISTING |
| | SERVICE IS TOO SMALL TO ACCOMMODATE THE LOAD. PROVIDE |
| | CORRECTION. NEC 215.2, 220, FBC RE3602.1 (THE LAUNDRY |
| | CIRCUIT MUST BE CALCULATED AT 1500 VA. ALTHOUGH THIS |
| | DOESN'T CHANGE THE SERVICE SIZE, PROVIDE CORRECTION SO |
| | RECORDS ARE CORRECT.) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. PROVIDE PANEL SCHEDULE/SIZING FOR ALL PANELS. |
| | INDICATE ANY NEW OR ALTERED CIRCUITS, AFCI OR GFCI |
| | PROTECTION AS REQUIRED. NEC 215.5, 408.4, 408.30 FBC |
| | RE3706.1 (PANEL SP SHOWS THE WATER HEATER ON A 30 AMP |
| | BREAKER. BASED ON 125% OF THE LOAD, THIS BREAKER SHOULD |
| | BE A 25 AMP. PROVIDE CORRECTION. ALSO, THE NEW PANEL SP |
| | DOES NOT INDICATE AFCI OR GFCI AS REQUESTED. A NOTE |
| | WILL SUFFICE, STATING: "ALL 120-VOLT, SINGLE PHASE, 15 |
| | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| | RE3902.12") |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. PROVIDE DETAILS OF SAUNA. DOES THIS REQUIRE GFCI |
| | PROTECTION? NEC 110.3; FBC 107.2.1 (DETAILS AND/OR SPEC |
| | SHEETS NOT PROVIDED, AND THERE IS CONFLICTING |
| | INFORMATION ON PLAN. THERE IS A STATEMENT ON PLAN THAT |
| | "SAUNA DOES NOT REQUIRE POWER, CONTROLS ARE BATTERY |
| | POWERED". HOWEVER, THE PANEL SCHEDULE SHOWS A 30 AMP |
| | CIRCUIT WITH A 5300 VA LOAD FOR THE SAUNA. PROVIDE |
| | PREVIOUSLY REQUESTED INFORMATION AND CORRECT PLAN.) |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY DESIGN |
| | PROFESSIONAL. FS 471, FAC61G15-23, FBC 107.3.5 (ONE SET |
| | OF PLANS STILL HAS THE OLD ELECTRICAL DRAWING. BOTH |
| | SETS NEED THE CORRECTED DRAWING, SIGNED AND SEALED.) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |