Plan Review Notes
Plan Review Notes For Permit 17061148
Permit Number 17061148
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-14 15:09:27CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. BASED ON THE LOAD CALCULATION PROVIDED, THE EXISTING
 SRVICE IS TOO SMALL TO ACCOMODATE THE LOAD. PROVIDE
 CORRECTION. NEC 215.2, 220, FBC RE3602.1
 2. 2/0 WIRE FROM MBP TO MLC IS TOO SMALL. THIS WIRE
 SIZE CAN ONLY BE USED WHEN IT SERVES 100% OF THE LOAD.
 PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE3602.2
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. PROVIDE PANEL SCHEDULE/SIZING FOR ALL PANELS.
 INDICATE ANY NEW OR ALTERED CIRCUITS, AFCI OR GFCI
 PROTECTION AS REQUIRED. NEC 215.5, 408.4, 408.30 FBC
 RE3706.1
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3
 7. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION
 FOR AC/HVAC. NEC 334.80; FBC RE3705.4.4
 8. PROVIDE DETAILS OF SAUNA. DOES THIS REQUIRE GFCI
 PROTECTION? NEC 110.3; FBC 107.2.1
 9. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 10. LIGHTING IN PORCH AREAS SHALL BE SUITABLE FOR DAMP
 LOCATIONS. PROVIDE COMPLIANCE. NEC 410.10; FBC RE4003.9
 11. THE CURRENT CODE BEING USED IS THE 2011 NEC, PLEASE
 CORRECT NOTES. FBC PREFACE, 107.2.1
 12. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL. FS 471, FAC61G15-23, FBC 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  