| 2017-07-14 15:09:27 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. BASED ON THE LOAD CALCULATION PROVIDED, THE EXISTING |
| | SRVICE IS TOO SMALL TO ACCOMODATE THE LOAD. PROVIDE |
| | CORRECTION. NEC 215.2, 220, FBC RE3602.1 |
| | 2. 2/0 WIRE FROM MBP TO MLC IS TOO SMALL. THIS WIRE |
| | SIZE CAN ONLY BE USED WHEN IT SERVES 100% OF THE LOAD. |
| | PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE3602.2 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 5. PROVIDE PANEL SCHEDULE/SIZING FOR ALL PANELS. |
| | INDICATE ANY NEW OR ALTERED CIRCUITS, AFCI OR GFCI |
| | PROTECTION AS REQUIRED. NEC 215.5, 408.4, 408.30 FBC |
| | RE3706.1 |
| | 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE. |
| | SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING |
| | OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3 |
| | 7. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL |
| | WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION |
| | FOR AC/HVAC. NEC 334.80; FBC RE3705.4.4 |
| | 8. PROVIDE DETAILS OF SAUNA. DOES THIS REQUIRE GFCI |
| | PROTECTION? NEC 110.3; FBC 107.2.1 |
| | 9. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC |
| | 410.16(B), FBC RE4003.12 |
| | 10. LIGHTING IN PORCH AREAS SHALL BE SUITABLE FOR DAMP |
| | LOCATIONS. PROVIDE COMPLIANCE. NEC 410.10; FBC RE4003.9 |
| | 11. THE CURRENT CODE BEING USED IS THE 2011 NEC, PLEASE |
| | CORRECT NOTES. FBC PREFACE, 107.2.1 |
| | 12. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY DESIGN |
| | PROFESSIONAL. FS 471, FAC61G15-23, FBC 107.3.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |