Plan Review Notes
Plan Review Notes For Permit 17061148
Permit Number 17061148
Review Stop B
Sequence Number 1
Notes
Date Text
2017-07-21 18:56:41RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE PROPOSED GARAGE SHOWS A DOOR LEADING TO THE
 EXISTING MASTER BEDROOM. GARAGE LEADING TO A BEDROOM IS
 NOT ALLOWED. REVISE PLANS AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4
 FBC-RESIDENTIAL.
  
 4- IT LOOKS LIKE THE WINDOWS TYPE AND SIZE SPECIFIED
 FOR THE SECOND FLOOR BEDROOMS DON'T COMPLY WITH THE
 MINIMUM OPENING AREA AND MINIMUM OPENING HEIGHT OF THE
 EGRESS REQUIREMENTS. REVISE AS REQUIRED TO COMPLY. OR
 PROVIDE WINDOW MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE. SEC. R310.1.1 AND SEC. R310.1.2
 FBC-RESIDENTIAL.
  
 5- SPECIFY ROOF CROSS VENTILATION FOR THE NEW GARAGE AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL.
  
 6- OVERHEAD DOOR JAMB DETAIL 2/A6:
 A) FASTENING SPECIFICATIONS ARE FOR BLOCK CONSTRUCTION.
 THE FRAMING FOR THE GARAGE DOOR IS WOOD. REVISE AS
 REQUIRED TO MATCH PLANS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) DETAIL SPECIFIES (3)2X4 STUDS. STUD BEARING WALL
 FRAMING DETAIL 3/A6 SPECIFIES. (4) 2X4 STUDS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- THE LIVE LOAD OF THE SECOND FLOOR SPECIFIED ON THE
 GRAVITY LOADS ON SHEET S1 NEED TO BE REVISED TO COMPLY
 WITH TABLE R301.5 FBC-RESIDENTIAL.
  
 8- ACCORDING TO SEC. R301.2.1.4 THIS BUILDING IS
 LOCATED IN EXPOSURE "C" NOT EXPOSURE "B". REVISE THE
 SURFACE ROUGHNESS, EXPOSURE CATEGORY AND HEIGHT
 ADJUSTMENT COEFFICIENT ON THE WIND LOAD FACTORS ON
 SHEET S1.
  
 9- UPDATE THE YEAR OF ALL THE STANDARDS REFERENCED ON
 THE CONCRETE AND MASONRY WALLS NOTES ON SHEET S1. SEE
 CHAPTER 46 OF THE FBC-RESIDENTIAL FOR CURRENT YEAR OF
 EACH STANDARD AND REVISED AS REQUIRED.
  
 10- SHEET S2: SPECIFY ROOF SLOPE FOR NEW ROOF OVER
 PATIO AS REQUIRED BY SEC. R905.11.1 FBC-RESIDENTIAL.
  
 11- EXTERIOR ELEVATIONS ON SHEET A4 AND DOOR SCHEDULE
 ON SHEET A2 SPECIFIES DOOR "C" TO BE FIBERGLASS SOLID
 DOOR. DOOR NOA 14-1117.05 SUBMITTED IS FOR ALUMINUM
 DOOR WITH GLAZING. PLANS AND PRODUCT APPROVAL NEED TO
 MATCH. DOOR WITH GLAZING NEEDS TO BE CONSIDERED IN THE
 ENERGY CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 12- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) NEED THE NAME AT THE BOTTOM OF FORM OF THE PERSON
 PREPARING THE CALCULATIONS AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING CORRECT OWNER'S NAME AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) THIS IS A TWO STORY ADDITION. SPECIFY THE FLOOR AREA
 OF THE SECOND FLOOR ON ITEM #8. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) THIS IS A TWO STORY ADDITION. REVISE THE UNDER ATTIC
 AREA SPECIFIED ON ITEM #10. THE UNDER ATTIC AREA IS THE
 AREA ABOVE THE SECOND FLOOR. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 F) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 TO
 MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. IT'S NOT
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) DOORS INFORMATION ON PAGE 3 OF 4 NEED TO BE
 COORDINATED WITH PLANS AND PRODUCT APPROVAL SUBMITTED.
 COORDINATE WITH ITEM #11 ABOVE. REVISE AS REQUIRED TO
 MATCH. DOOR WITH GLASS NEEDS TO BE CONSIDERED WITH THE
 WINDOWS AREAS AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION.
  
 H) GARAGE AREA SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 GARAGE AREA SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL REQUIRED FOR THE DOORS AND WINDOWS SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS IS REQUIRED WHEN CALCULATIONS DON'T USE
 THE DEFAULT FACTORS FOR GLAZING.
  
 13- ALL THE PLANS NEED TO BE SIGNED, SEALED AND DATED
 BY THE ARCHITECT OF RECORD. SEC. 61G1-16.001 FAC.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF. AND CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED. NOTE: IF THE DESIGN
 PRESSURES OF THE SELECTED ASSEMBLY DON'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) CEMENT BOARD SOFFIT AND TRIM AS SPECIFIED ON PLANS.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL
 (INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 16- DESIGNER OF RECORD TO SPECIFY CARBON MONOXIDE
 ALARMS FOR ALL THE BEDROOMS IN THE EXISTING HOUSE AS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]