| 2017-08-15 08:34:35 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS (2ND REVIEW): |
| | |
| | PREVIOUS COMMENTS NOT ADDRESSED, SEE BELOW; |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY DESIGN PROFESSIONAL OR THE ELECTRICAL |
| | CONTRACTOR QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5 |
| | 2. SHOW ON PLAN THE LOCATION OF ANY EXISTING SMOKE |
| | ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATION. FBC 907.2.11 |
| | 3. SHOW ON PLAN ANY NEW OR ALTERED CIRCUITS AND OUTLETS |
| | REQUIRED FOR WALL SPACE IN NEW WALLS. NEC 210.52 |
| | 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED |
| | CIRCUITS, SHOW WIRE AND BREAKER SIZE, INDICATE AFCI OR |
| | GFCI PROTECTION AS REQUIRED. NEC 210.8, 210.12, 215.5; |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |