| 2017-06-28 08:54:13 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. SHOW PANEL AND SERVICE LOACTION ON PLAN. FBC 107.2.1 |
| | 2. SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION FOR |
| | LIGHTING AND POWER OUTLETS. C401.2.1 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION FOR EACH |
| | STRUCTURE, INCLUDING ALL LOADS REQUIRED PER CODE. NEC |
| | 220 |
| | 4. EACH STRUCTURE WILL REQUIRE SEPARATE PERMIT, PROVIDE |
| | AS REQUESTED PREVIOUSLY. FBC 105.1 |
| | 5. IT APPEARS THAT THERE ARE SEVERAL CIRCUITS FEEDING |
| | THE DETACHED GARAGE FROM THE HOUSE PANEL. PER CODE: "A |
| | BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A BRANCH |
| | CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT". PROVIDE CORRECTION. NEC |
| | 225.30 |
| | 6. PROVIDE GROUNDING ELECTRODE SYSTEM FOR BUILDING |
| | SUPPLIED BY A FEEDER. NEC 250.32 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |