2017-06-28 08:54:13CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHOW PANEL AND SERVICE LOACTION ON PLAN. FBC 107.2.1
 2. SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION FOR
 LIGHTING AND POWER OUTLETS. C401.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION FOR EACH
 STRUCTURE, INCLUDING ALL LOADS REQUIRED PER CODE. NEC
 220
 4. EACH STRUCTURE WILL REQUIRE SEPARATE PERMIT, PROVIDE
 AS REQUESTED PREVIOUSLY. FBC 105.1
 5. IT APPEARS THAT THERE ARE SEVERAL CIRCUITS FEEDING
 THE DETACHED GARAGE FROM THE HOUSE PANEL. PER CODE: "A
 BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A BRANCH
 CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT". PROVIDE CORRECTION. NEC
 225.30
 6. PROVIDE GROUNDING ELECTRODE SYSTEM FOR BUILDING
 SUPPLIED BY A FEEDER. NEC 250.32
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  