| 2017-06-29 12:30:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) WILL THIS PROPOSED GENERATOR PROVIDE BACKUP |
| | EMERGENCY POWER TO ANY LIFE SAFETY SYSTEM.I.E FIRE |
| | ALARM OR FIRE SPRINKLER? |
| | |
| | IF SO, IT SHALL COMPLY WITH NFPA 110. PLEASE PROVIDE AN |
| | APPLICABLE NOTE AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 2) THE ATTACHED DATA SHEETS INDICATE THE PROPOSED WILL |
| | BE FUELED BY LP AND/OR NG. PLEASE CONFIRM. |
| | |
| | THE FUEL SUPPLY SHALL BE UNDER SEPARATE PERMIT IF NOT |
| | DONE BY THIS CONTRACTOR OR SPECIFICALLY INDENTIFIED |
| | UNDER THIS PERMIT WILL ALL APPLICABLE DRAWINGS SHOWING |
| | LOCATION AND SIZE OF ALL PIPE CONNECTIONS, LOCATION AND |
| | SIZE OF PROPOSED PIPE, DEPTH OF COVER, ETC., AND |
| | EQUIPMENT SPEC SHEETS. |
| | |
| | |
| | |
| | 3) THE ARE NO DRAWINGS OF FOUNDATION PLANS OR HOW IT |
| | WILL BE SECURED TO THE FOUNDATION. THERE ARE NO |
| | DIMENSIONS FROM THE BUILDING. |
| | |
| | PLEASE PROVIDEAND ENSURE COMPLIANCE WITH THE APPLICABLE |
| | CODE. |
| | |
| | |
| | |
| | 4) PLEASE PROVIDE DIMENSIONS OF THE NEAREST WINDOW AND |
| | OR DOOR TO ENSURE THE SEPARATION DISTANCES REQUIRED |
| | THAT AVOIDS FUMES ENTERING THE BUILDING. THERE IS NO |
| | INDICATION OF EXHAUST LOCTION. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |