| Plan Review Notes For Permit 17061037 |
| Permit Number |
17061037 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-31 09:42:09 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061037 | | | 7/31/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW EXHAUST HOOD HAS A CAPACITY OF 600 CFMS | | | WHICH REQUIRES MAKEUP AIR TO BE PROVIDED PER SECTION | | | 505.2. PLEASE REVISE THE PLAN TO SHOW HOW THE AIR WILL | | | BE PROVIDED, AND SHOW THE EXHAUST DUCT RUN AND POINT OF | | | CONNECTION TO THE EXISTING DUCT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|