| Plan Review Notes For Permit 17061034 |
| Permit Number |
17061034 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-26 14:45:53 | PERMIT # 17061034 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | 1) THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE | | | ADDRESS PROVIDED ON THE PERMIT APPLICATION. | | | | | | 2) SHEET 1.2A: OCCUPANT LOAD CALCULATIONS DO NOT MATCH | | | DETAILS PROVIDED ON PLANS. DINING AREA IS LISTED AS 157 | | | SQ. FT. WITH AN OCC LOAD OF 10. | | | DRAWINGS SHOW / OUTLINE 209 SQ FT OCCUPIED BY TABLES | | | AND CHAIRS, WITH SEATING FOR A MINIMUM OF 27. | | | SHEET C-1 LISTS NUMBER OF SEATS AS "26". PLEASE REVIEW | | | AND REVISE DETAILS TO SHOW ACCURATE CALCULATIONS AND | | | OCCUPANY LOADS ON ALL RELEVANT SHEETS. | | | | | | 3) SHEET 1.1A: PER EQUIPMENT PLAN DETAILS, ONLY | | | EQUIPMENT THAT WILL BE USED FOR HEATING OF FOODS ARE | | | TWO (2) RICE COOKERS. | | | PLEASE VERIFY AND CONFIRM THAT NO ADDITIONAL COOKING | | | EQUIPMENT WILL BE USED. | | | PLEASE NOTE THAT ANY COOKING THAT MAY PRODUCE GREASE | | | LADEN VAPORS WILL REQUIRE INSTALLATION OF AN APPROVED | | | HOOD SUPPRESSION SYSTEM. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|