| 2017-06-29 09:26:14 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17061034 |
| | ADD: 310 S. DIXIE HWY. SUITE 300 & 302 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 973-941-7444 |
| | E-MAIL: ?????? WE PREFER E-MAIL FOR CORRESPONDENCE!!! |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 29 |
| | ACTION: DENIED |
| | |
| | 1) SHEET D-1: |
| | 1A) SHEET D-1 SHOWS THE FRONT ENTRY WALL (BOWED WALL) |
| | BEING REMOVED AN APPROXIMATE 30 FOOT SECTION OF WALL. |
| | SHEET 1.0A SHOWS A STRAIGHT SECTION OF WALL WITH |
| | APPROX.. A 45 DEGREE TURN AND A 42 INCH SECTION OF |
| | WALL, 2 WINDOWS AND ONE DOOR AND SHEET 1.3A THE |
| | ELEVATION SHEET SHOWS A TRANSOM HORIZONTAL MULLION, |
| | WINDOWS AND DOOR. PLEASE PROVIDE A CUT SECTION THROUGH |
| | THIS PORTION OF NEW WALL. ON THE EXTERIOR CEILING THERE |
| | WILL BE CEILING MISSING SINCE THE BOWED FRONT WAS |
| | REMOVED, HOW WILL THIS NEW WALL SECTION TIE INTO THE |
| | FLOOR FRAMING SYSTEM? THE PLANS INDICATE USE THE |
| | EXISTING HEADER? TYPE OF MATERIAL? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED? THIS WALL SECTION WILL BE PART |
| | OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) PLEASE |
| | SHOW CONNECTIONS FBC-B 1609.6.4. |
| | |
| | 1B) THIS SAME WALL SECTION SHOWS THE TRANSOM ABOVE AND |
| | A HORIZONTAL FRAMING MEMBER SEPARATING THE TRANSOM |
| | ABOVE FROM THE DOOR AND WINDOWS BELOW. WHAT SUPPORTS |
| | THE HORIZONTAL FRAMING MEMBER AT THE 45 DEGREE TURN? IS |
| | THERE A COLUMN NOT SHOWN, OR A 45 DEGREE ALUMINUM |
| | MULLION? PLEASE SHOW THE VERTICAL FRAMING MEMBER AS |
| | WELL, AND SHOW HOW BOTH THE HORIZONTAL AND VERTICAL |
| | FRAMING MEMBERS ARE GOING TO BE ANCHORED. MAYBE |
| | CONSIDERED AS MWFRS OR COMPONENTS AND CLADDING |
| | DEPENDING ON THE MATERIALS USED AND IF THERE IS PRODUCT |
| | APPROVALS. |
| | |
| | 1C) SHEET 1.3A SECTION 3-1.3A SHOWS THE TRANSOM LITES |
| | AND HEADER NOT BEING MOVED, THEN WHAT MATERIAL WILL BE |
| | USED FOR INFILL BETWEEN THE BOWED SECTION ABOVE THAT |
| | STAYS AND THE NEW SECTION BELOW THAT SHOWS A STRAIGHT |
| | SECTION OF WALL WITH A 45 DEGREE TURN AN 42 INCH |
| | SECTION OF WALL?107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | IF THIS DETAIL IS NOT CORRECTLY ILLUSTRATED AND THE |
| | TRANSOMS ARE TO BE REUSED AND REINSTALLED PLEASE |
| | PROVIDE THE INFORMATION ON THE WINDOW SASH, HOW WILL |
| | THEY BE RE-INSTALLED, DOES THE PRESENT GLAZING MEET THE |
| | WIND DESIGN PRESSURES OF TODAY, AND WITH BEING |
| | REINSTALLED HOW WILL THEY MEET THE REQUIREMENTS FOR |
| | LARGE MISSILE IMPACT TESTING OR BE SHUTTERED. |
| | 1609.6.4.4 APPLICATIONS OF WIND PRESSURE. |
| | 2404.1 VERTICAL GLASS. |
| | 2) SHEET 1.3A THE WIND DESIGN CRITERIA IS GIVEN |
| | CORRECTLY BUT NOT THE PRESSURES ASSOCIATED WITH THE |
| | DESIGN. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (5.) DESIGN WIND |
| | PRESSURES. |
| | 3) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) SHEET 1.0A DOOR # 1 IS MISSING ON THE PLANS & DOOR # |
| | 6 IS THIS A INTERIOR DOOR NEEDING FIRE RATING OR IS |
| | THIS A EXTERIOR DOOR? 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 7) SHEET1.2A THE REAR EXIT DOOR FROM THE DINING AREA |
| | DOES NOT HAVE THE REQUIRED 18 INCHES AT THE LATCH SIDE |
| | OF THE DOOR. PLEASE SHOW COMPLIANCE WITH: 2014 FBC |
| | ACCESSIBILITY CODE 404.2.4 OR |
| | 404.3 AUTOMATIC AND POWER-ASSISTED DOORS AND GATES. |
| | 404.3.2 MANEUVERING CLEARANCE. |
| | CLEARANCES AT POWER-ASSISTED DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. CLEARANCES AT AUTOMATIC DOORS AND |
| | GATES WITHOUT STANDBY POWER AND SERVING AN ACCESSIBLE |
| | MEANS OF EGRESS SHALL COMPLY WITH 404.2.4. |
| | |
| | EXCEPTION: WHERE AUTOMATIC DOORS AND GATES REMAIN OPEN |
| | IN THE POWER-OFF CONDITION, COMPLIANCE WITH 404.2.4 |
| | SHALL NOT BE REQUIRED. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |