2017-06-23 14:36:371901 SOUTH FLAGLER DRIVE
 PERMIT #17061006
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A SEPARATE PERMIT IS NEEDED FOR THE BACKFLOW PREVENTER.
  
 PLANS INDICATE OUTDATED FLOW TEST DATA FOR 720 8TH
 STREET.
  
 RISER DETAIL INDICATES 1-1/4" CHECK AND CONTROL VALVES
 ON A 4-INCH RISER.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 NO PRODUCT CUT SHEETS SUBMITTED FOR SPRINKLER SYSTEM
 COMPONENTS OR UNDERGROUND PIPING.
  
 INDICATE HOW THE UNDERGROUND PIPING WILL BE RESTRAINED
 FROM MOVEMENT. IF UTILIZING JOINT RESTRAINTS, SUBMIT
 PRODUCT DATA INDICATING REQUIRED TORQUE.
  
 INADEQUATE SPRINKLER PROTECTION PROVIDED AT THE TOP OF
 THE TWO INTERNAL STAIRS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  