| 2017-12-13 11:03:56 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061005 | | | 12/13/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | MANY OF THE PREVIOUS COMMENTS STILL EXIST. PER | | | TELEPHONE CONVERSATION WITH MIGUEL OF GLIDDEN-SPINA THE | | | CIMMENTS LISTED BELOW ARE UNDERSTOOD AND WILL BE | | | ADDRESSED ON THE NEXT PLAN SUBMISSION. | | | | | | 1) SHEETS: A1.1 & A1.3 STILL SHOW THE AC CLOSET DOOR | | | OPENING INTO THE KITCHEN. | | | | | | 2) SHEET A2 IS STILL INDICATING THE AC CLOSET DOOR TO | | | BE WOOD AND NOT NON-COMBUSTIBLE. | | | | | | 3) REQUESTED AC COOLING AND HEATING CALCULATIONS NIT | | | SUBMITTED. | | | | | | 4) UL 197 LISTING AND LABELING FOR THE ELECTRIC COOKING | | | APPLIANCE NOT VERIFIED ON THE VENTLESS HOOD SUBMITTAL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|