| Permit Number |
17061005 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-03 14:53:18 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061005 | | | 7/3/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE VENTLESS | | | COOKING SYSTEM- SECTION 917.1. | | | | | | 2) EXHAUST VENTILATION AT A RATE OF .070 CFMS PER | | | SQ.FT. IS REQUIRED FOR THE KITCHEN PER TABLE 403.3, AND | | | RECIRCULATION OF AIR FROM THE SPACE IS PROHIBITED PER | | | FOOTNOTE B. THE CURRENT PLAN IS NOT IN COMPLIANCE- | | | PLEASE CORRECT. | | | | | | 3) M0.1: THE OUTSIDE AIR CALCULATIONS FOR "OFFICES" ARE | | | NOT APPLICABLE TO THE PROPOSED OCCUPANCY WHICH IS CAFE | | | OR DINING/KITCHEN. | | | | | | 4) M2.1: A LOUVERED AC CLOSET DOOR IS INDICATED, | | | HOWEVER THE DOOR SCHEDULE ON A2 INDICATES A SOLID WOOD | | | DOOR- SEE SECTION C403.2.7.2 FBC-14 ENERGY COMPLIANCE | | | AND SECTION 602.2.1- A NON-COMBUSTIBLE DOOR IS | | | REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|