| 2017-07-05 08:51:47 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE NOTE FOR EXIT AND EMERGENCY LIGHTS TO BE |
| | CONNECTED AHEAD OF TIMECLOCK CONTROL. NEC 700.12(F) |
| | 2. PROVIDE SERVICE OUTLET FOR CU-1. NEC 210.63 |
| | 3. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT WITH |
| | LIGHTING CONTROL. NEC 210.62; FBC C405.2.3 |
| | 4. LOAD CALCULATION IN PANEL SCHEDULE PROVIDED EXCEEDS |
| | THE VALUE OF THE TRANSFORMER FEEDING THE UNIT. PROVIDE |
| | CORRECTION. NEC 110.3 |
| | 5. LOAD CALCULATION IN PANEL SCHEDULE PROVIDED SHOWS |
| | THE SAME RATING FOR ALL REFRIGERATORS AND KITCHEN |
| | EQUIPMENT. PROVIDE SPEC SHEETS WITH DETAILS OF LOAD FOR |
| | EACH PIECE OF EQUIPMENT AND REVISE LOAD CALCULATION TO |
| | REFLECT THE ACTUAL LOADS. NEC 110.3, 215.5, 220 |
| | 6. PROVIDE DETAIL OF INTERIOR LIGHTING POWER |
| | REQUIREMENTS IN RELATION TO THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC C405.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |