| Plan Review Notes For Permit 17061004 |
| Permit Number |
17061004 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-14 14:26:27 | FAILED | | | | | | PROVIDE WRITTEN RESPONSES. | | | | | | 1) THE PROVIDED SITE PLAN SHOWS THE CURRENT PARKING LOT | | | LAYOUT ADJACENT TO EXCHANGE COURT AND THE FPU METER IN | | | WHAT IS NOW THE LANDSCAPE BUFFER. THIS BUFFER WILL BE | | | REMOVED AS PART OF THE CONSTRUCTION OF THE NEW | | | BENTLEY/ROLLS ROYCE BUILDING AND INSTEAD BECOME A DRIVE | | | AISLE. ARE YOU PLANNING TO INSTALL THE GAS METER AND | | | LINE AND THEN RELOCATE THEM WITHIN THE NEXT YEAR WHEN | | | THE DRIVEWAY ENTRANCE IS REDONE? IT SEEMS LIKE A BETTER | | | IDEA TO LOCATE THE METER AND LINE IN ITS FINAL LOCATION | | | AND ONLY DO THE CONSTRUCTION ONE TIME. | | | | | | 2) THE GAS METER IS NOT PERMITTED IN THE BUFFER WHERE | | | IT WOULD ALLOW A GAP IN THE REQUIRED HEDGE. PROVIDE | | | VERIFICATION THAT THE HEDGE IS NOT INTERRUPTED BY THE | | | GAS METER IN WHICHEVER LOCATION IT ENDS UP. | | | | | | 3) THE NEW GENERATOR REQUIRES SCREENING FOR THE FULL | | | HEIGHT OF THE GENERATOR. | | | | | | 4) PROVIDE THE GENERATOR DIMENSIONS ON THE PLAN, AS | | | WELL AS THE DIMENSIONS FROM THE GENERATOR TO THE | | | BUILDING, ELECTRICAL ROOM, ETC. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | 2017-07-12 09:14:24 | ROUTED TO ERIC SCHNEIDER |
|