| Notes |
| Date |
Text |
| 2017-10-24 11:50:32 | MECHANICAL PROVISO: | | | CCOLE- 10/24/2017 | | | | | | 1) REVISONS TO THE MECHANICAL PLAN SHEETS M3.1 & M6.1 | | | ARE REQUIRED TO CORRECT THE VRF RISER DIAGRAM, AND THE | | | AC EQUIPMENT SCHEDULE SO THAT THE SYSTEMS MATCH THE | | | PLANS AND MANUFACTURER'S CUT SHEETS. |
|