| 2017-07-13 12:13:42 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17060989 |
| | ADD: 101 N. CLEMATIS ST. SUITE: 200 |
| | CONT: BSA CORP. |
| | TEL: 561-272-6350 / KIM UNKE |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 13/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0.1.1. NOTE NUMBER 31 MAKES REFERENCE TO THE |
| | CITY OF MIAMI FIRE DEPARTMENT REGULATIONS. PLEASE |
| | UPDATE PLANS TO THE WEST PALM BEACH FIRE DEPARTMENT |
| | REGULATIONS. 107.2.1.3. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 2) SHEET ALS1.1 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | |
| | 3) SHEET A1.1.1: |
| | 3A) DOORS 202 & 216 ARE BOTH POCKET DOORS SHEET A2.01 |
| | DOOR SCHEDULE AND HARDWARE GROUP LABELED # 9. |
| | THE HARDWARE GROUP WILL NEED TO SHOW COMPLIANCE |
| | WITH2014 FBC-ACCESSIBILITY CODE 404.2.7 DOOR AND GATE |
| | HARDWARE. WHERE SLIDING DOORS ARE IN THE FULLY OPEN |
| | POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND |
| | USABLE FROM BOTH SIDES. |
| | ADVISORY 404.2.7 DOOR AND GATE HARDWARE. DOOR HARDWARE |
| | THAT CAN BE OPERATED WITH A CLOSED FIST OR A LOOSE GRIP |
| | ACCOMMODATES THE GREATEST RANGE OF USERS. HARDWARE THAT |
| | REQUIRES SIMULTANEOUS HAND AND FINGER MOVEMENTS REQUIRE |
| | GREATER DEXTERITY AND COORDINATION, AND IS NOT |
| | RECOMMENDED. |
| | |
| | 3B) PRIVATE RESTROOMS 215 AND 225 ARE TO BE CONSIDERED |
| | ADAPTABLE THE PLANS WILL NEED TO SHOW COMPLIANCE WITH |
| | THE ACCESSIBILITY CODE 604.5 GRAB BARS EXCEPTION # 1. |
| | GRAB BARS SHALL NOT BE REQUIRED TO BE INSTALLED IN A |
| | TOILET ROOM FOR A SINGLE OCCUPANT ACCESSED ONLY THROUGH |
| | A PRIVATE OFFICE AND NOT FOR COMMON USE OR PUBLIC USE |
| | PROVIDED THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS |
| | AND LOCATED SO AS TO PERMIT THE INSTALLATION OF GRAB |
| | BARS COMPLYING WITH 604.5. |
| | ACCESSIBILITY CODE 609.4 POSITION OF GRAB BARS. 609.8 |
| | STRUCTURAL STRENGTH. |
| | ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS |
| | USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS |
| | IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, |
| | MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| | |
| | 3C) PRIVATE RESTROOMS 215 AND 225 ARE TO BE CONSIDERED |
| | ADAPTABLE THE PLANS WILL NEED TO SHOW COMPLIANCE WITH |
| | THE ACCESSIBILITY CODE 604.3.1 (SIZE / CLEARANCE AROUND |
| | THE WATER CLOSET, 60 INCHES) & 604.3.2.(OVERLAP). WITH |
| | THE BATHROOMS BEING REQUIRED TO BE ADAPTABLE THE |
| | FIXTURE LAYOUT WILL NEED TO AND WASTE LINES WILL NEED |
| | TO BE INSTALLED AS IF AN ACCESSIBLE BATHROOM, TO BE |
| | CONSIDERED ADAPTABLE. FOR CHAPTER 6 FOR EACH CODE |
| | REQUIREMENT IF THERE IS AN EXCEPTION FOR PRIVATE |
| | BATHROOMS OR RESTROOMS THERE IS AN EXCEPTION STATING AS |
| | SUCH, NONE GIVEN FOR EITHER OF THE ABOVE CODE SECTIONS, |
| | MAKING THE LAYOUT OF FIXTURES WITH CLEARANCES A |
| | REQUIREMENT, BACKING A REQUIREMENT AND FIXTURE LOCATION |
| | A REQUIREMENT, TO MAKE THE UNIT AN ADAPTABLE UNIT. |
| | |
| | 3D) PRIVATE RESTROOMS 215 AND 225 ARE TO BE CONSIDERED |
| | ADAPTABLE THE PLANS WILL NEED TO SHOW COMPLIANCE WITH |
| | THE ACCESSIBILITY CODE FOR A STANDARD ROLL-IN TYPE |
| | SHOWER COMPARTMENT. |
| | AGAIN FOR A ADAPTABLE SHOWER THE PLANS WILL NEED TO |
| | SHOW WHERE THE BACKING WILL BE PLACED FOR POSSIBLE |
| | FUTURE GRAB BARS INCOMPLIANCE WITH ACCESS. CODE 608.3 |
| | EXCEPTION # 1. |
| | |
| | 3E) PLEASE INDICATE HOW COMPLIANCE WITH EITHER 608.3.2 |
| | STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS OR 608.3.3 |
| | ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS WILL BE |
| | ACHIEVED. |
| | |
| | 3F) PLEASE PROVIDE COMPLIANCE WITH THE SHOWER: |
| | 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. IN |
| | STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE |
| | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| | LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| | INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS |
| | PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT |
| | SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO THE |
| | SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM |
| | THE SEAT WALL. |
| | |
| | OR |
| | |
| | 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| | LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| | INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS |
| | PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT |
| | SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT |
| | 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR |
| | SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15 |
| | INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE |
| | SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY. |
| | |
| | 3G) 2014 ACCESSIBILITY CODE 608.7 THRESHOLDS. |
| | THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE |
| | 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2 |
| | INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR |
| | VERTICAL. |
| | |
| | 4) SHEET A1.1.3: |
| | 4A) SUSTAINABLE NOTE WALL COVERING LIST COMPLIANCE WITH |
| | THE 2007/2009 SUPPLEMENTS SECTION |
| | 803. PLEASE UPDATE CODE DATA TO THE CURRENT 2014 FBC-B. |
| | |
| | 4B) FLOOR FINISHES ARE NOT GIVEN. 2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA, |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES FLOOR FINISHES & TRIM MISSING (FLAME |
| | SPREAD/SMOKE DEVELOPMENT). |
| | |
| | 5) SHEET A2.01 DOOR AND WINDOW TYPES SHOW VARIOUS |
| | SECTIONS THROUGH THE FRAME AND GLAZING, SECTIONS 2-11, |
| | MISSING THESE SECTIONS NOT FOUND ON THIS SHEET. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |