| 2017-08-25 11:04:57 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17060979 |
| | ADD: 525 S. FLAGLER DR. 3RD FLOOR |
| | CONT: L J SHEEHAN INC. |
| | TEL: 561-223-2750 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. AUGUST 25/ 2017 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4) BUILDING PROVISO/ DEFERRED SUBMITTAL: NANA WALL |
| | SYSTEM. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | |
| | 5) BUILDING PROVISO/ DEFERRED SUBMITTAL: PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 |
| | FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1 |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 7A) 2ND REQUEST. THE PLANS DO NOT INDICATE IF THERE IS |
| | PROTECTION FROM DRIVING RAIN. SEE 1ST ROUND OF |
| | COMMENTS. |
| | 1ST ROUND COMMENTS. 1710.5.1.1FBC-B EXTERIOR WINDOWS |
| | AND DOORS. (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED |
| | WHERE THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN |
| | 1 NEED NOT BE TESTED FOR WATER INFILTRATION. THE |
| | OVERHANG RATIO SHALL BE CALCULATED BY THE FOLLOWING |
| | EQUATION: |
| | OH RATIO = OH LENGTH/OH HEIGHT |
| | WHERE: |
| | OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN |
| | OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. |
| | OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM |
| | THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A |
| | DOOR. |
| | |
| | 7B) PLEASE BE ADVISED WITH THE USE OF NANA WALL SYSTEM, |
| | IN THE OUTSWING DOOR SYSTEM NOA 15-0226.05 HAS A ADA |
| | COMPLIANT SILL, AND WITH THE ADA COMPLIANT SILL THERE |
| | IS A NOTE THAT THE DOORS ARE NOT APPROVED WHERE WATER |
| | RESISTANCE IS REQUIRED, PAGE 7 OF 8 IN THE NOA. THE |
| | OTHER SILL HEIGHT OF THE PRODUCT APPROVAL PAGE 6 OF 8 |
| | IS APPROXIMATELY 2 ? INCHES IN HEIGHT. SHEET A2.0.2. |
| | SHOWS A SILL WITH A HEIGHT OF 4 INCHES, PLEASE HAVE |
| | NANA WALL PROVIDE A LETTER ON THEIR LETTER HEAD STATING |
| | A 4 INCH HIGH SILL IS AVAILABLE WITH THIS SYSTEM. |
| | PLEASE PROVIDE HOW THE 4 INCH SILL IS GOING TO MEET THE |
| | REQUIREMENTS OF THE ACCESSIBILITY CODE UNDER SECTION |
| | 404.2.4 OF THE 2014 ACCESSIBILITY CODE. |
| | |
| | 7C) PLEASE NOTE WITH NANA DOOR PRODUCT APPROVAL NOA |
| | 15-0226.05 WILL NOT MEET THE PRESSUES FOR THE DOORS |
| | LOCATED IN ZONE # 5. SHEET A2.01 INDICATES NEGAITIVE |
| | PREUUSRES OF - 131.1 FOR 20 SQ. FT. IN ZONE 5. THE |
| | TECHNICAL SHEET 1OF 8 IN THE NOA INDICATES THE HIGHEST |
| | NEGATIVE PRESSURES OF -90 TO THE LOWEST NEGATIVE |
| | PRESSURES OF -70 DEPENDING ON THE PANEL SIZE. |
| | |
| | 1ST ROUND OF COMMENTS. THERE ARE 2 ISSUES, THE PLANS DO |
| | NOT PROVIDE A CUT SECTION THROUGH THE INTERIOR FINISH |
| | FLOOR, TRACK AND THE EXTERIOR FINISH FLOOR WITH NEW |
| | TILE. SHEET A2.02 DOOR & HARDWARE NOTE NUMBER 14 |
| | INDICATES ALL THRESHOLDS SHALL HAVE NO STEP GREATER |
| | THAN ? INCH PER A.D.A. REQUIREMENTS. WITH NOT SEEING |
| | THE PRODUCT APPROVAL FOR THE EURO WALL SYSTEM THIS MAY |
| | OR MAY NOT BE AN ISSUE BUT A LOT OF THESE DOOR SYSTEMS |
| | HAVE DISCLAIMERS LIKE, WHEN AN ADA/ FLUSH SILL IS USED, |
| | THESE DOORS ARE NOT APPROVED FOR THE USE WHERE WATER |
| | INFILTRATION RESISTANCE IS REQUIRED. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 8) SHEET A2.01; |
| | 8A-8B) COMPLIED. |
| | |
| | 8C) 2ND REQUEST. SHEET A2.01. DOOR 328B IN ANY POSITION |
| | SHALL NOT REDUCE THE REQUIRED WIDTH BY ONE-HALF OF THE |
| | REQUIRED EGRESS WIDTH. FBC-B 1005.7.1. YOU CAN RECESS |
| | THE DOOR FURTHER INTO THE CLOSET TO GET THE ONE HALF OF |
| | THE REQUIRED WIDTH. |
| | |
| | 1ST ROUND OF COMMENTS. DOOR 328B BLOCKS THE EGRESS |
| | PATH, MUST COMPLY WITH FBC-B 1005.7 ENCROACHMENT. |
| | ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH |
| | SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS |
| | SECTION. |
| | 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT |
| | REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178 |
| | MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE |
| | REQUIRED WIDTH BY MORE THAN ONE-HALF. |
| | |
| | 8D) 2ND REQUEST. PLEASE NOTE THE REVISED PLAN SHOWS THE |
| | STAIRWELLS AT THE ENDS OF THE BUILDING BUT THERE IS NO |
| | SEPARATION OF AN ELEVATOR LOBBY FROM THE CORRIDOR. THE |
| | ELEVATOR LOBBY IS CONTINUOUS SINCE SMOKE CAN GO FROM |
| | THE ELEVATOR SHAFT AND FILL UP THE CORRIDOR. THAT IS |
| | WHY YOU EITHER PRESSURIZE THE ELEVATOR SHAFT OR MEET |
| | ONE OF THE OTHER EXCEPTIONS PROVIDED IN FBC-B 713.14.1 |
| | OR EXCEPTIONS. |
| | |
| | 1ST ROUND OF COMMENTS. PLEASE PROVIDE AN OVERALL FLOOR |
| | PLAN FOR THIS FLOOR. IF THE WORK AREA IS OVER 50 % OF |
| | THE FLOOR PLATE THEN |
| | PLEASE SHOW COMPLIANCE WITH THE 2014 EXISTING BUILDING |
| | CODE 803.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING |
| | ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY |
| | FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE |
| | ENCLOSURE REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO |
| | VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE |
| | FLOOR. THE 2007 EXISTING COMMENTARY ON THE EXISTING |
| | BUILDING CODE SPEAKS ABOUT THE FIRST TIME THE CODE |
| | REQUIRES WORK OUTSIDE OF THE TENANT SPACE. SINCE THE |
| | DESIGNER OF RECORD IS ALREADY WORKING OUTSIDE OF THE |
| | TENANT SPACE THIS COMMENT IF OVER 50 % OF THE FLOOR |
| | PLATE IS BEING CONSIDERED THE WORK AREA THEN THIS |
| | COMMENT STANDS. |
| | THE PLANS DO NOT SHOW WHERE EITHER OF THE TENANT SPACES |
| | HAVE AT LEAST ONE MEANS OF EGRESS WITH NOT GOING |
| | THROUGH THE ELEVATOR LOBBY. 2014 FBC-B 713.14.1 AND |
| | EXCEPTIONS 1-7, PLEASE PROVIDE CODE COMPLIANCE. |
| | |
| | 9-10) COMPLIED. |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |