| 2017-07-20 07:58:01 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT |
| | NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA, |
| | WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL |
| | SUFFICE. WPB AMENDMENTS TO FBC 107.3.5 |
| | 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 |
| | AND ASHREA 90.1: 8.4.2 |
| | 3. ALL RECEPTACLES IN KITCHEN AREAS (ROOM 311) REQUIRE |
| | GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2) |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL IN THE NEW LOCATION TO CONFIRM THE STATED AIC |
| | RATING OF THE PANELS IS ADEQUATE. NEC 110.9, 110.10 |
| | 5. DATA/PHONE ROOM 315 DOES NOT SHOW ANY POWER OUTLETS. |
| | HOW WILL THE EQUIPMENT IN THIS ROOM GET POWER? PLEASE |
| | CLARIFY AND/OR CORRECT. FBC 107.2.1 |
| | 6. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES |
| | PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED |
| | INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC |
| | C405.5, 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |