2017-09-07 10:53:343RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17060969
 9/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS #2, 3, & 4 FROM THE PREVIOUS REVIEW STILL
 EXIST. I HAVE REPRINTED THE COMMENTS BELOW- PLEASE
 COMPLY,
  
 2) SHEET M1: IT APPEARS THAT AIR FROM AHU'S1 & 2 IS
 BEING TRANSFERRED FORM THE OFFICES BACK INTO THE
 CORRIDOR WHICH IS PROHIBITED PER SECTION 601.2. PLEASE
 NOTE THAT THE TRANSFER DUCT SIZES ARE NOT INDICATED.
  
 3) SHEET M1, AHU-1: A) THE PLAN INDICATES 1550 CFMS OF
 SUPPLY AIR FROM A 3-TON SYSTEM WHICH APPEARS TO EXCEED
 A TYPICAL 3-TON UNIT'S CAPACITY. B) THE 14 " MAIN TRUNK
 IS UNDERSIZED FOR 1450 CFMS AT TYPICAL 0.1: W.C.
 FRICTION LOSS.
  
 4) M1, AHU-5: A) THE PLAN INDICATES 2300 CFMS OF SUPPLY
 AIR FROM A 2-1/2-TON SYSTEM WHICH EXCEEDS THE CAPACITY
 OF THE SYSTEM. B) THE 14" AND 12" DUCTS ARE UNDERSIZED
 FOR 2300 AND 1200 CFMS AT A TYPICAL 0.1" W.C FRICTION
 LOSS.
  
 5) NEW COMMENT: THE NEW AC PLAN REQUIRES THE SIGNATURE
 OF THE PERSON WHO PREPARED IT- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC- . ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER