| Plan Review Notes For Permit 17060969 |
| Permit Number |
17060969 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-09-07 10:53:34 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060969 | | | 9/7/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENTS #2, 3, & 4 FROM THE PREVIOUS REVIEW STILL | | | EXIST. I HAVE REPRINTED THE COMMENTS BELOW- PLEASE | | | COMPLY, | | | | | | 2) SHEET M1: IT APPEARS THAT AIR FROM AHU'S1 & 2 IS | | | BEING TRANSFERRED FORM THE OFFICES BACK INTO THE | | | CORRIDOR WHICH IS PROHIBITED PER SECTION 601.2. PLEASE | | | NOTE THAT THE TRANSFER DUCT SIZES ARE NOT INDICATED. | | | | | | 3) SHEET M1, AHU-1: A) THE PLAN INDICATES 1550 CFMS OF | | | SUPPLY AIR FROM A 3-TON SYSTEM WHICH APPEARS TO EXCEED | | | A TYPICAL 3-TON UNIT'S CAPACITY. B) THE 14 " MAIN TRUNK | | | IS UNDERSIZED FOR 1450 CFMS AT TYPICAL 0.1: W.C. | | | FRICTION LOSS. | | | | | | 4) M1, AHU-5: A) THE PLAN INDICATES 2300 CFMS OF SUPPLY | | | AIR FROM A 2-1/2-TON SYSTEM WHICH EXCEEDS THE CAPACITY | | | OF THE SYSTEM. B) THE 14" AND 12" DUCTS ARE UNDERSIZED | | | FOR 2300 AND 1200 CFMS AT A TYPICAL 0.1" W.C FRICTION | | | LOSS. | | | | | | 5) NEW COMMENT: THE NEW AC PLAN REQUIRES THE SIGNATURE | | | OF THE PERSON WHO PREPARED IT- SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FBC- . ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|