Plan Review Notes
Plan Review Notes For Permit 17060969
Permit Number 17060969
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-14 15:56:442ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060969
 8/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER WHO SIGNED AND SEALED THE RESUBMITTED
 AC PLAN MUST PROVIDE A TITLE BLOCK ON THE PLAN- SECTION
 61G15-23.002 FAC.
  
 2) SHEET M1: IT APPEARS THAT AIR FROM AHU'S1 & 2 IS
 BEING TRANSFERRED FORM THE OFFICES BACK INTO THE
 CORRIDOR WHICH ISNPROHIBITED PER SECTION 601.2. PLEASE
 NOTE THAT THE TRANSFER DUCT SIZES ARE NOT INDICATED.
  
 3) SHEET M1, AHU-1: A) THE PLAN INDICATES 1550 CFMS OF
 SUPPLY AIR FROM A 3-TON SYSTEM WHICH APPEARS TO EXCEED
 A TYPICAL 3-TON UNIT'S CAPACITY. B) THE 14 " MAIN TRUNK
 IS UNDERSIZED FOR 1450 CFMS AT TYPICAL 0.1: W.C.
 FRICTION LOSS.
  
 4) M1, AHU-5: A) THE PLAN INDICATES 2300 CFMS OF SUPPLY
 AIR FROM A 2-1/2-TON SYSTEM WHICH EXCEEDS THE CAPACITY
 OF THE SYSTEM. B) THE 14" AND 12" DUCTS ARE UNDERSIZED
 FOR 2300 AND 1200 CFMS AT A TYPICAL 0.1" W.C FRICTION
 LOSS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER