2017-06-30 10:05:441ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17060969
 6/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PLANS ARE DEFICIENT. IN ORDER TO
 EXPEDITE THE SECOND REVIEW, PLEASE PROVIDE THE
 FOLLOWING:
  
 A) A SCOPE OF WORK OUTLINE- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC
 B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES AFFECTED BY THE ALTERATIONS- SECTIONS 809.1 &
 809.2 FBC-14 EXISTING BUILDING.
 C) AC COOLING AND HEATING CALCULATIONS. IF SYSTEMS ARE
 REPLACEMENTS CALCULATIONS ARE NOT REQUIRED, HOWEVER AC
 CHANGEOUT FORMS AND AHRI CERTIFICATES MUST BE
 SUBMITTED- SECTION C403.2.1 ENERGY CONSERVATION.
 D) AC EQUIPMENT SCHEDULES- 107.2.1
 E) AC EQUIPMENT LOCATIONS AND INSTALLATION DETAILS.
 PLEASE NOTE THAT WIND LOAD ENGINEERING IS REQUIRED FOR
 EXTERIOR CONDENSER INSTALLATIONS- SECTION 301.15 FBC-15
 MECHANICAL.
 F) AIR DEVICE SCHEDULE- 107.2.1, SECTION 603 FBC-14
 MECHANICAL.
 G) RETURN AIR PLENUM DETAILS- SECTION 602.
 H) DUCT SUPPPORT AND CONNECTIO N DETAILS PER SMACNA
 STANDARDS
 I) ACCESS FOR SERVICE AND REPLACEMENT OF THE ABOVE
 CEILING AIR HANDLERS- SECTION 306.1.
 J) CONDENSATE DISPOSAL PLANS FOR THE AIR HANDLERS-
 SECTION 307.
  
 2) PLEASE NOTE THAT FURTHER COMMENTS MAY OCCUR AT
 SECOND REVIEW. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  