| 2017-06-30 10:05:44 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES |
| | PERMIT #17060969 |
| | 6/30/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE MECHANICAL PLANS ARE DEFICIENT. IN ORDER TO |
| | EXPEDITE THE SECOND REVIEW, PLEASE PROVIDE THE |
| | FOLLOWING: |
| | |
| | A) A SCOPE OF WORK OUTLINE- SECTION 107.2.1 WPB |
| | AMENDMENTS TO THE FBC |
| | B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES AFFECTED BY THE ALTERATIONS- SECTIONS 809.1 & |
| | 809.2 FBC-14 EXISTING BUILDING. |
| | C) AC COOLING AND HEATING CALCULATIONS. IF SYSTEMS ARE |
| | REPLACEMENTS CALCULATIONS ARE NOT REQUIRED, HOWEVER AC |
| | CHANGEOUT FORMS AND AHRI CERTIFICATES MUST BE |
| | SUBMITTED- SECTION C403.2.1 ENERGY CONSERVATION. |
| | D) AC EQUIPMENT SCHEDULES- 107.2.1 |
| | E) AC EQUIPMENT LOCATIONS AND INSTALLATION DETAILS. |
| | PLEASE NOTE THAT WIND LOAD ENGINEERING IS REQUIRED FOR |
| | EXTERIOR CONDENSER INSTALLATIONS- SECTION 301.15 FBC-15 |
| | MECHANICAL. |
| | F) AIR DEVICE SCHEDULE- 107.2.1, SECTION 603 FBC-14 |
| | MECHANICAL. |
| | G) RETURN AIR PLENUM DETAILS- SECTION 602. |
| | H) DUCT SUPPPORT AND CONNECTIO N DETAILS PER SMACNA |
| | STANDARDS |
| | I) ACCESS FOR SERVICE AND REPLACEMENT OF THE ABOVE |
| | CEILING AIR HANDLERS- SECTION 306.1. |
| | J) CONDENSATE DISPOSAL PLANS FOR THE AIR HANDLERS- |
| | SECTION 307. |
| | |
| | 2) PLEASE NOTE THAT FURTHER COMMENTS MAY OCCUR AT |
| | SECOND REVIEW. WHEN RESUBMITTING, IT IS HELPFUL TO |
| | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |